| Plan Review Notes For Permit 12060397 |
| Permit Number |
12060397 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-26 11:35:34 | ***PROVISOS*** | | | ***ISSUED AT CONTRACTOR'S RISK*** | | | ***REVISION REQUIRED**** | | | | | | | | | 1. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD | | | ZONE. ELEVATION OF MECHANICAL EQUIPMENT IS TO BE 6" | | | ABOVE BFE. SHOW PROPOSED HEIGHT ON PLAN. THIS SHOULD | | | ALSO BE INCLUDED ON ELEVATION CERTIFICATE, CONSTRUCTION | | | DRAWINGS, WPB ADMIN CODE 94-546(B). | | | | | | SUBMIT ELEVATION CERTIFICATE WITH ENERGY CALCS | | | | | | 2. ENERGY CALCS, ITEM 12, SIZE OF UNITS NOT CONSISTENT | | | WITH PLAN WHICH SHOWS 25,800 BTU. | | | | | | SUBMIT REVISED ENERGY CALCS AS A REVISION | | | | | | | | | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | | 561-805-6732 | | | |
|