| Plan Review Notes For Permit 12060397 |
| Permit Number |
12060397 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-20 16:42:22 | 1. RETURN IS SHOWN IN KITCHEN, PLEASE SEE FBC | | | 1602.2(4), PROHIBITED LOCATIONS AND REVISE PLAN. | | | | | | 2. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD | | | ZONE. ELEVATION OF MECHANICAL EQUIPMENT IS TO BE 6" | | | ABOVE BFE. SHOW PROPOSED HEIGHT ON PLAN. THIS SHOULD | | | ALSO BE INCLUDED ON ELEVATION CERTIFICATE, CONSTRUCTION | | | DRAWINGS, WPB ADMIN CODE 94-546(B). | | | | | | 3. ENERGY CALCS, ITEM 12, SIZE OF UNITS NOT CONSISTENT | | | WITH PLAN WHICH SHOWS 25,800 BTU. | | | | | | 4. THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN | | | IS TO INCLUDE NAME, LICENSE NUMBER, AND SIGNATURE ON | | | THE PLAN FS489. | | | | | | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | | 561-805-6732 | | | |
|