| Plan Review Notes For Permit 12060388 |
| Permit Number |
12060388 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-09-04 11:33:46 | COMMENTS FROM FIRST AND SECOND REVIEWS HAVE NOT BEEN | | | ADDRESSED. | | | | | | 2010 FBC & 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) ON SHEET E-1 0 THROUGH E-1 3 NOTE 1 UNDER ELECTRICAL | | | SPECIFICATIONS REFERENCES THE 2007 FBC W/2009 | | | REVISIONS. PLEASE UPDATE TO THE 2010 FBC. CITY | | | AMENDMENTS 107.2.1 | | | | | | 2) THE NOTE BELOW THE LOAD CALCULATIONS ON THE | | | ELECTRICAL PLAN SHEETS SPECIFIES THE 2005 NEC. PLEASE | | | UPDATE TO THE 2008 NEC. CITY AMENDMENTS 107.2.1 | | | | | | 3) THE RECEPTACLE ON THE CEILING FOR THE OVERHEAD | | | GARAGE DOOR OPENER IS REQUIRED TO BE GFCI PROTECTED PER | | | 2008 NEC ART.210.8 (A). | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|