| 2012-06-23 17:15:36 | 8321 OKEECHOBEE BOULEVARD |
| | PERMIT #12060388 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF |
| | BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | ALL NEW APARTMENTS AND TOWNHOUSES SHALL BE PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM PER SECTION 30.3.5.1 (NFPA 101 - |
| | FLORIDA EDITION 2009). |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED (BY DESIGN PROFESSIONAL) FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. |
| | |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |
| | |
| | |
| | |
| | |