| Plan Review Notes For Permit 12060374 |
| Permit Number |
12060374 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-16 14:18:54 | FBC PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET A0.0 SHOWS TOTAL OCCUPANCY OF 3508 OCCUPANTS. | | | FBC PLUMBING 2010 403.1.1 TO DETERMINE THE OCCUPANT | | | LOAD OF EACH SEX THE TOTAL OCCUPANT LOAD SHALL BE | | | DIVIDED IN HALF. | | | TABLE 403.1 MERCANTILE 1754 MEN WOULD REQUIRE 4 WATER | | | CLOSETS OR UP TO 50% URINALS, WOMEN 4 WATER CLOSETS, | | | AND ONE UNISEX TOILET PER 403.5. TOTAL = 9 | | | PLEASE LIST THE EXISTING FIXTURES TO COMPARE WITH THE | | | REQUIRED FACILITIES FOR THE COMBINED BUILDINGS. | | | | | | 2. SHEET P2.1 FOR THE CAFE AREA A GREASE TRAP OR | | | INTERCEPTOR MAY BE REQUIRED DEPENDING UPON WHAT IS | | | BEING PREPARED. | | | 1003.3.1 A GREASE INTERCEPTOR OR AUTOMATIC GREASE | | | REMOVAL DEVICE SHALL BE REQUIRED TO RECEIVE THE | | | DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN | | | WASTE LOCATED IN FOOD PREPARATION AREAS... THAT ALLOW | | | FATS, OILS OR GREASE TO BE DISCHARGED. | | | | | | ADVISORY: | | | IRRIGATION IS NOT PART OF THIS REVIEW. A SEPARATE | | | APPLICATION, PLAN. REVIEW, AND PERMIT WILL BE REQUIRED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|