| 2012-06-23 20:26:11 | 2101 PALM BEACH LAKES BOULEVARD |
| | 107,000 SQ.FT. CLASS "A" MERCANTILE OCCUPANCY |
| | PERMIT #12060374 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FIRE LANES SHALL BE HAVE PAINTED CURB MARKINGS AND BE |
| | MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO |
| | PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL |
| | BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS |
| | AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE |
| | BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE |
| | TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| | FLORIDA FIRE PREVENTION CODE SECTION 18.2.3.5.3. |
| | |
| | TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE |
| | SITE DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN |
| | DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR |
| | CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS |
| | POSTED. |
| | |
| | WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR |
| | SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| | |
| | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| | |
| | SHEET A2.3: FOR CLASS A MERCANTILE OCCUPANCIES, PROVIDE |
| | AND MAINTAIN AT LEAST ONE AISLE 60-INCHES WIDE LEADING |
| | DIRECTLY TO AN EXIT. |
| | |
| | SHEET A2.3: PROVIDE PERMANENT BOLLARDS IN ADDITION TO |
| | FLOOR MARKINGS FOR THE 44-INCH WIDE EGRESS AISLE |
| | LOCATED IN THE STOCKROOM/STAGING AREA. |
| | |
| | SHEET C4: FIRE HYDRANTS SHALL BE PROVIDED WITH |
| | CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4' TO |
| | THE BACKSIDE PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA |
| | EDITION. THESE CLEARANCES MAY AFFECT A FEW PARKING |
| | SPACES. |
| | |
| | SHEET FS1.1: CITY FURNITURE AND ASHLEY FURNITURE ARE |
| | LOCATED IN SEPARATE, STAND-ALONE BUILDINGS SHARING A |
| | COMMON 4-HOUR FIRE WALL; THEREFORE, EACH BUILDING NEEDS |
| | ITS OWN FIRE WATER SERVICE, BACKFLOW PREVENTER AND |
| | SPRINKLER SYSTEM. |
| | |
| | SHEET FS2.1: THE CONSTRUCTION DOCUMENTS ESTABLISH |
| | MIRCEA PELLA AS THE ENGINEER OF RECORD FOR THE FIRE |
| | SPRINKLER DESIGN, THEREFORE, THE SPRINKLER SHOP |
| | DRAWINGS SHALL NOT BE SIGNED/SEALED BY THE CONTRACTOR'S |
| | ENGINEER. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |