| Plan Review Notes For Permit 12060356 |
| Permit Number |
12060356 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-21 15:27:53 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THIS PARCEL IS LOCATED IN EXPOSURE D, PLEASE REVISE | | | ENGINEERING FBC 1609. | | | | | | 2. PRESSURES CIRCLED FOR A 90FT BUILDING, PRESSURES | | | SPECIFIED IN CONTRACTOR'S WINDOW SCHEDULE DO NOT | | | CORRELATE WITH ENGINEERING. PROVIDE BUILDING HEIGHT; | | | THIS BUILDING EXCEEDS 90'. REVISE; FBC 107. | | | | | | 3. ON THE PRODUCT APPROVALS, INDICATE WHICH METHOD OF | | | INSTALLATION WILL BE USED TO COMPLY WITH REQUIRED | | | DESIGN PRESSURES, FBC 1609. |
|