Plan Review Notes
Plan Review Notes For Permit 12060340
Permit Number 12060340
Review Stop B
Sequence Number 2
Notes
Date Text
2012-08-03 18:51:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. OK
  
 2. DESIGN PRESSURES FOR BUILDINGS OVER 60 FEET ARE TO
 BE DETERMINED BY A DESIGN PROFESSIONAL USING ASCE7-10,
 FBC 1609.1, FS471.
  
 NOT ALL OPTIONS OF THE PROPOSED DOOR COMPLY WITH THE
 DESIGN PRESSURES SPECIFIED. PLEASE MARK THE OPTIONS
 PROPOSED ON THE PRODUCT APPROVAL TO SHOW COMPLIANCE
 WITH DPS SPECIFIED BY ARCHITECT (-120.3 PSF IS THE
 WORST CASE).
  
 THIS MAY BE SUBMITTED VIA EMAIL IF SENT BY TUESDAY,
 AUGUST 7TH (WILL HOLD AT MY DESK FOR TWO BUSINESS DAYS)
 OR AT THE COUNTER IF THAT IS MORE CONVENIENT FOR
 CONTRACTOR.
  
 3. PROVIDE INFORMATION REGARDING THE FLOOR COVERING
 AND, IF ALL OF THE FLOOR COVERING IS NOT CARPET,
 PROVIDE INFORMATION REGARDING THE PROPOSED FLOORING
 (MATERIAL, THICKNESS), SHOW COMPLIANCE WITH SOUND
 TRANSMISSION FBC 1207.2 AND FBC 1207.3, AND COMPLIANCE
 WITH FLAME SPREAD < 200 FBC 603.1(2).
  
 PLEASE BE ADVISED THAT THIS PERMIT WILL BE ISSUED WITH
 THE DOCUMENT SUBMITTED; HOWEVER, IN THE FUTURE, THE
 TEST RESULT WILL BE REQUIRED OR ADVISE WHERE IN THE
 CODE THIS IS EXEMPTED - US FLOORS NATURAL CORK
 UNDERLAYMENT.
  
 **NEW COMMENT**
  
 4. PLAN SHOWS THAT FIRE SPRINKLERS MAY BE AFFECTED.
 THIS PERMIT WILL REQUIRE FIRE PLAN REVIEW; ADVISORY
 ONLY.
  