Plan Review Notes
Plan Review Notes For Permit 12060340
Permit Number 12060340
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-12 12:23:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A PLAN WHICH SHOWS SCOPE OF ALL WORK
 PROPOSED. FOR INSTANCE, THE APPLICATION STATES "MINOR
 FRAMING & DRYWALL MODIFICATION," NO SUCH WORK SHOWN. NO
 WINDOW/DOOR REPLACEMENT SHOWN ON THE PLAN.
  
 2. DESIGN PRESSURES FOR BUILDINGS OVER 60 FEET ARE TO
 BE DETERMINED BY A DESIGN PROFESSIONAL USING ASCE7-10,
 FBC 1609.1, FS471.
  
 3. PROVIDE INFORMATION REGARDING THE FLOOR COVERING
 AND, IF ALL OF THE FLOOR COVERING IS NOT CARPET,
 PROVIDE INFORMATION REGARDING THE PROPOSED FLOORING
 (MATERIAL, THICKNESS), SHOW COMPLIANCE WITH SOUND
 TRANSMISSION FBC 1207.2 AND FBC 1207.3, AND COMPLIANCE
 WITH FLAME SPREAD < 200 FBC 603.1(2).
  
  
  