2012-08-26 16:26:163101 VILLAGE BOULEVARD - CLUBHOUSE
 PERMIT #12060339
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AS A SUBSTITUTE FOR PANIC HARDWARE, ONLY THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 IF THE EXISTING SET OF DOUBLE DOORS LEADING TO THE POOL
 DO NOT HAVE PANIC HARDWARE, THEN THE OTHER REQUIRED
 EXIT DOORS FROM THE CLUBHOUSE MUST HAVE PANIC HARDWARE.
  
 IF THE EXISTING SET OF DOUBLE DOORS LEADING TO THE POOL
 ARE EQUIPPED WITH PANIC HARDWARE, THEN THE SINGLE
 EXTERIOR EXIT DOOR (NORTH) CAN BE CONSIDERED THE MAIN
 ENTRANCE WHEREBY PANIC HARDWARE IS NOT REQUIRED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE