| Plan Review Notes For Permit 12060339 |
| Permit Number |
12060339 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-08-26 16:26:16 | 3101 VILLAGE BOULEVARD - CLUBHOUSE | | | PERMIT #12060339 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | AS A SUBSTITUTE FOR PANIC HARDWARE, ONLY THE MAIN | | | ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR | | | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING | | | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS | | | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN | | | HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE | | | SUBSTITUTED FOR A KEYED LOCK. | | | | | | IF THE EXISTING SET OF DOUBLE DOORS LEADING TO THE POOL | | | DO NOT HAVE PANIC HARDWARE, THEN THE OTHER REQUIRED | | | EXIT DOORS FROM THE CLUBHOUSE MUST HAVE PANIC HARDWARE. | | | | | | IF THE EXISTING SET OF DOUBLE DOORS LEADING TO THE POOL | | | ARE EQUIPPED WITH PANIC HARDWARE, THEN THE SINGLE | | | EXTERIOR EXIT DOOR (NORTH) CAN BE CONSIDERED THE MAIN | | | ENTRANCE WHEREBY PANIC HARDWARE IS NOT REQUIRED. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE |
|