2012-06-18 10:32:513101 VILLAGE BOULEVARD - CLUBHOUSE
 PERMIT #12060339
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 PROVIDE RAMP AND HANDRAIL DETAILS FOR NEW RAMP.
  
 COOKING EQUIPMENT IS REQUIRED TO BE PROTECTED BY A TYPE
 I EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC SUPPRESSION
 SYSTEM (WET CHEMICAL).
  
 PROVIDE SAFETY INFORMATION AND EQUIPMENT CUT-SHEETS FOR
 PROPOSED ELECTRIC FIRE PLACE.
  
 NOTE:
 VERIFY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 VERIFY EXISTING PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  