| 2012-07-06 10:26:35 | BUILDING PLAN REVIEW |
| | PERMIT: 12060339 |
| | ADD: 3101 VILLAGE BLVD- CLUBHOUSE |
| | CONT: BISHOP |
| | TEL: (561)312-1024 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS (SHEET A2.1) INDICATE THE REPLACEMENT OF |
| | GLAZED OPENINGS, PLEASE SHOW CODE COMPLIANCE WITH |
| | 1609.4.4.1 AND RULE 9N-3 . |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS |
| | |
| | 3) WITH THE REPLACEMENT OF EXTERIOR WINDOWS & DOORS THE |
| | PLANS WILL NEED TO DESIGN THE CRITERIA FOR WIND DESIGN. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 4) SHEET A2.1 INDICATES A NEW WOOD TRELLIS, A6.01 |
| | PROVIDES SCHEMATIC DETAILS OF TRELLIS, NOT ENOUGH |
| | INFORMATION HOW THE MWFRS WILL TRANSFER THROUGH TO THE |
| | FOUNDATION BELOW, MISSING TIE DOWNS ON THE 2X2 CROSS |
| | MEMBERS, ALL 2X8 HORIZONTAL FRAMING MEMBERS & 2X112 |
| | CEDAR BEAMS TO COLUMNS BELOW, NOTE THE FOUNDATION |
| | DETAIL PROVIDES THE STEEL IN THE FOUNDATION AND BOTTOM |
| | POST BASE BUT THERE IS NO VERTICAL STEEL INDICATED FOR |
| | THE PIER. |
| | |
| | 5) SHEET A2.1 ALSO INDICATES A NEW METAL FRAME AND |
| | CANVAS STRUCTURE OVER THE EXISTING CABANA BAR, THERE IS |
| | NO FRAMING INFORMATION PROVIDED, SEPERATE PLANS AND |
| | REVIEWS WILL BE REQUIRED. |
| | |
| | 6) SHEET A2.1 INDICATES NEW NON-BEARING WALLS NO |
| | DETAILS WERE PROVIDED, 2010 FBC-B 107.3.5.1.1. MINIMUM |
| | CRITERIA FOR COMMERCIAL PLAN REVIEW. |
| | |
| | 7) SHEET A2.1 INDICATES BOTH THE USE OF GLASS WALLS AND |
| | GLAZING IN SWING DOORS, 2010 FBC-B 2406.4 (1-2). |
| | |
| | 8) PLANS DO NOT PROVIDE THE OCCUPANT LOAD, 2010 FBC-B |
| | MINIMUM CRITERIA FOR COMMENRCIAL PLAN REVIEW, & |
| | 1008.1.10 PANIC HARDWARE. |
| | |
| | 9) SHEET A2.1 THE NEW HANDICAPPED RAMP IS APPROXIMATELY |
| | 8'-0" LONG, 2010 FBC-B 11-405.7.3 PLANS DO NOT INDICATE |
| | A BOTTOM LANDING. |
| | |
| | 10) SHEET A2.1 THE NEW HANDICAPPED RAMP DOES NOT |
| | INDICATE COMPLIANCE WITH 11-405.7.8 RAMPS WITH A RISE |
| | GREATER THAN 6" SHALL HAVE HANDRAILS COMPLYING WITH |
| | 505. |
| | |
| | 11) PLANS DO NOT PROVIDE A SITE PLAN SHOWING AN |
| | ACCESSIBLE DROP OFF ZONE, DROPPED CURB OR ACCESSIBLE |
| | PARKING SPACE PLEASE SHOW COMPLIANCE WITH: |
| | |
| | 2010 FBC-B 11-4.202.4.1 ALTERATIONS TO AN AREA |
| | CONTAINING A PRIMARY FUNCTION. IN ADDITION TO THE |
| | REQUIREMENTS OF SECTION 11-4.1.6(1), AN ALTERATION THAT |
| | AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS TO |
| | AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO |
| | AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE |
| | PATH OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS, |
| | TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED |
| | AREA, ARE READILY ACCESSIBLE TO AND USABLE BY |
| | INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS |
| | ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN |
| | TERMS OF COST AND SCOPE. |
| | |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION |
| | TO THE PRIMARY FUNCTION AREA. |
| | |
| | DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | |
| | (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE |
| | PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. |
| | |
| | (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | |
| | (I) AN ACCESSIBLE ENTRANCE; |
| | |
| | (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| | |
| | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM: |
| | |
| | (IV) ACCESSIBLE TELEPHONES; |
| | |
| | (V) ACCESSIBLE DRINKING FOUNTAINS; AND |
| | |
| | (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH |
| | AS PARKING, STORAGE, AND ALARMS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |