2012-07-06 10:26:35BUILDING PLAN REVIEW
 PERMIT: 12060339
 ADD: 3101 VILLAGE BLVD- CLUBHOUSE
 CONT: BISHOP
 TEL: (561)312-1024
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS (SHEET A2.1) INDICATE THE REPLACEMENT OF
 GLAZED OPENINGS, PLEASE SHOW CODE COMPLIANCE WITH
 1609.4.4.1 AND RULE 9N-3 .
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
  
 3) WITH THE REPLACEMENT OF EXTERIOR WINDOWS & DOORS THE
 PLANS WILL NEED TO DESIGN THE CRITERIA FOR WIND DESIGN.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) SHEET A2.1 INDICATES A NEW WOOD TRELLIS, A6.01
 PROVIDES SCHEMATIC DETAILS OF TRELLIS, NOT ENOUGH
 INFORMATION HOW THE MWFRS WILL TRANSFER THROUGH TO THE
 FOUNDATION BELOW, MISSING TIE DOWNS ON THE 2X2 CROSS
 MEMBERS, ALL 2X8 HORIZONTAL FRAMING MEMBERS & 2X112
 CEDAR BEAMS TO COLUMNS BELOW, NOTE THE FOUNDATION
 DETAIL PROVIDES THE STEEL IN THE FOUNDATION AND BOTTOM
 POST BASE BUT THERE IS NO VERTICAL STEEL INDICATED FOR
 THE PIER.
  
 5) SHEET A2.1 ALSO INDICATES A NEW METAL FRAME AND
 CANVAS STRUCTURE OVER THE EXISTING CABANA BAR, THERE IS
 NO FRAMING INFORMATION PROVIDED, SEPERATE PLANS AND
 REVIEWS WILL BE REQUIRED.
  
 6) SHEET A2.1 INDICATES NEW NON-BEARING WALLS NO
 DETAILS WERE PROVIDED, 2010 FBC-B 107.3.5.1.1. MINIMUM
 CRITERIA FOR COMMERCIAL PLAN REVIEW.
  
 7) SHEET A2.1 INDICATES BOTH THE USE OF GLASS WALLS AND
 GLAZING IN SWING DOORS, 2010 FBC-B 2406.4 (1-2).
  
 8) PLANS DO NOT PROVIDE THE OCCUPANT LOAD, 2010 FBC-B
 MINIMUM CRITERIA FOR COMMENRCIAL PLAN REVIEW, &
 1008.1.10 PANIC HARDWARE.
  
 9) SHEET A2.1 THE NEW HANDICAPPED RAMP IS APPROXIMATELY
 8'-0" LONG, 2010 FBC-B 11-405.7.3 PLANS DO NOT INDICATE
 A BOTTOM LANDING.
  
 10) SHEET A2.1 THE NEW HANDICAPPED RAMP DOES NOT
 INDICATE COMPLIANCE WITH 11-405.7.8 RAMPS WITH A RISE
 GREATER THAN 6" SHALL HAVE HANDRAILS COMPLYING WITH
 505.
  
 11) PLANS DO NOT PROVIDE A SITE PLAN SHOWING AN
 ACCESSIBLE DROP OFF ZONE, DROPPED CURB OR ACCESSIBLE
 PARKING SPACE PLEASE SHOW COMPLIANCE WITH:
  
 2010 FBC-B 11-4.202.4.1 ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION. IN ADDITION TO THE
 REQUIREMENTS OF SECTION 11-4.1.6(1), AN ALTERATION THAT
 AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO
 AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE
 PATH OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS,
 TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED
 AREA, ARE READILY ACCESSIBLE TO AND USABLE BY
 INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS
 ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN
 TERMS OF COST AND SCOPE.
  
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved