Plan Review Notes
Plan Review Notes For Permit 12060310
Permit Number 12060310
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-06-15 11:38:27428 10TH STREET
 PERMIT #12060310
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE OCCUPANCY TYPE OF THIS BUILDING. DO EACH
 OF RENTAL UNITS HAVE SEPARATE COOKING FACILITIES? THE
 LAST OCCUPANCY ON RECORD (2002) AT THE FIRE DEPARTMENT
 IS FOR A LODGING/ROOMING HOUSE. INDICATE IF THE
 EXISTING FIRE ALARM SYSTEM FUNCTIONAL.
  
 PROVIDE A KEY PLAN. INDICATE WHERE UNIT #7 IS IN
 RELATION TO THE OTHER RENTAL UNITS.
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED. ALL DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 INDICATE HOW THE SMOKE ALARMS ARE POWERED.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  