| 2012-06-15 11:38:27 | 428 10TH STREET |
| | PERMIT #12060310 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | INDICATE THE OCCUPANCY TYPE OF THIS BUILDING. DO EACH |
| | OF RENTAL UNITS HAVE SEPARATE COOKING FACILITIES? THE |
| | LAST OCCUPANCY ON RECORD (2002) AT THE FIRE DEPARTMENT |
| | IS FOR A LODGING/ROOMING HOUSE. INDICATE IF THE |
| | EXISTING FIRE ALARM SYSTEM FUNCTIONAL. |
| | |
| | PROVIDE A KEY PLAN. INDICATE WHERE UNIT #7 IS IN |
| | RELATION TO THE OTHER RENTAL UNITS. |
| | |
| | DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF |
| | BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED. ALL DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | INDICATE HOW THE SMOKE ALARMS ARE POWERED. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |