| Plan Review Notes For Permit 12060310 |
| Permit Number |
12060310 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-15 12:13:11 | 12060310 | | | 428 10TH ST. | | | APARTMENT RENOVATIONS | | | | | | MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL | | | SERVICE IS LIMITED TO SIX SWITCHES GROUPED IN ONE | | | LOCATION. SHOW LOCATION OF METER AND DISCONNECT ON THE | | | STRUCTURE. NEC 230.70 | | | ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN | | | ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET | | | AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52 | | | GFCI PROTECTED OUTLETS UNIT ARE REQUIRED FOR EACH | | | DWELLING AT GRADE LEVEL FRONT AND BACK. NEC 210.52(E) | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. 2007 FBC R313 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|