| Notes |
| Date |
Text |
| 2012-10-10 15:52:01 | 12060405 | | | 428 10TH STREET | | | APARTMENT RENOVATIONS | | | | | | THE FOLLOWING COMMENT FROM THE PREVIOUS REVIEWS WAS NOT | | | ADDRESSED. | | | | | | SHEET E2 | | | THE 3/0 SERVICE FEEDERS APPEAR TO BE UNDER SIZED. | | | PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE. INDICATE THE CORRECTED SIZE OF THE MAIN | | | SERVICE DISCONNECT AND SERVICE FEEDERS. NEC 215.5, | | | 220.40 | | | | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | |
|