| Plan Review Notes For Permit 12060308 |
| Permit Number |
12060308 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-08-25 19:03:32 | 428 10TH STREET | | | PERMIT #12060308 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE LAST FIRE INSPECTION ON RECORD FOR THIS LOCATION | | | WAS IN 2002 FOR A ROOMING HOUSE. A RECENT AUGUST | | | INSPECTION CONFIRMED AN EXISTING ROOMING HOUSE | | | OCCUPANCY . DURING INSPECTION IT WAS OBSERVED THAT THE | | | BUILDING HAS BEEN SEVERLY DAMAGED BY VANDALS, WATER AND | | | POSSIBLY TERMITES. | | | | | | WHEN AN OCCUPANCY CHANGES FROM AN EXISTING ROOM HOUSE | | | TO NEW APARTMENTS, THE APARTMENT BUILDING IS REQUIRED | | | TO BE PROTECTED BY AN AUTOMATIC SUPERVISED FIRE | | | SPRINKLER SYSTEM. | | | | | | UPGRADING AND REPAIRING THE STAIRS NEEDS TO BE ADDED TO | | | PERMIT APPLICATION SCOPE OF WORK. GUARDS, AT LEAST | | | 42-INCHES TALL, SHALL BE PROVIDED AT THE OPEN SIDES OF | | | MEANS OF EGRESS (STAIRS, MEZZANINE, ETC.) THAT EXCEED | | | 30-INCHES ABOVE THE FLOOR. OPEN GUARDS SHALL PROHIBIT | | | THE PASSAGE OF A 4-INCH DIAMETER SPHERE UP TO A HEIGHT | | | OF 34-INCHES. THE TRIANGULAR OPENINGS FORMED BY THE | | | RISER, TREAD AND BOTTOM ELEMENT OF THE GUARDRAIL SHALL | | | PROHIBIT THE PASSAGE OF A 6-INCH DIAMETER SPHERE. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE |
|