 428 10TH STREET
 APARTMENT RENOVATIONS
  
 THE FOLLOWING COMMENTS WERE NOT ADEQUATELY ADDRESSED.
  
 PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE. NEC 215.5, 220.40
  
 MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL
 SERVICE IS LIMITED TO SIX GROUPED IN ONE LOCATION. A
 BUILDING SHALL BE SUPPLIED BY ONLY ONE SERVICE. NEC
 230.70, 230.2
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
  
 ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN
 ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET
 AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52
  