| 2012-08-14 15:59:58 | 12060405 | | | 428 10TH STREET | | | APARTMENT RENOVATIONS | | | | | | THE FOLLOWING COMMENTS WERE NOT ADEQUATELY ADDRESSED. | | | | | | PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE. NEC 215.5, 220.40 | | | | | | MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL | | | SERVICE IS LIMITED TO SIX GROUPED IN ONE LOCATION. A | | | BUILDING SHALL BE SUPPLIED BY ONLY ONE SERVICE. NEC | | | 230.70, 230.2 | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC | | | 110.9, 110.10 | | | | | | ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN | | | ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET | | | AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|