Plan Review Notes
Plan Review Notes For Permit 12060308
Permit Number 12060308
Review Stop B
Sequence Number 2
Notes
Date Text
2012-09-05 15:05:42BUILDING PLAN REVIEW
 PERMIT: 12060308
 ADD: 428 10TH STREET (FRONT)
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
 2010 FLORIDA BUILDING CODE/ BUILDING W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST, 2010 FBC-B 1209.2 ATTIC SPACES. AN
 OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM BY
 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 4) 2ND REQUEST, SHEET # 1 ROOM # 3, THE PLANS HAVE
 CHANGED FROM A DWELLING UNIT TO A EFFICIENCY UNIT WHICH
 IS COVERED UNDER SECTION 2010 FBC-B 1208.4.
 2010 FBC-B
 1208.4 EFFICIENCY DWELLING UNITS.
 AN EFFICIENCY LIVING UNIT SHALL CONFORM TO THE
 REQUIREMENTS OF THE CODE EXCEPT AS MODIFIED HEREIN:
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
 2. THE UNIT SHALL BE PROVIDED WITH A SEPARATE CLOSET.
 3. THE UNIT SHALL BE PROVIDED WITH A KITCHEN SINK,
 COOKING APPLIANCE AND REFRIGERATION FACILITIES, EACH
 HAVING A CLEAR WORKING SPACE OF NOT LESS THAN 30 INCHES
 (762 MM) IN FRONT. LIGHT AND VENTILATION CONFORMING TO
 THIS CODE SHALL BE PROVIDED.
 4. THE UNIT SHALL BE PROVIDED WITH A SEPARATE BATHROOM
 CONTAINING A WATER CLOSET, LAVATORY AND BATHTUB OR
 SHOWER.
 NOTE: THE BATHROOM AREA IS REMOVED FROM THE REQUIRED
 220 SQ FT FOR LIVING ROOM AREA. PLANS INDICATE WHEN
 SCALED APPROXIMATELY 205.5 SQ FT.
  
 1ST REVIEW: SHEET # 1 ROOM # 3 DOES NOT MEET THE
 REQUIREMENTS OF 2010 FBC-B 1208.3 ROOM AREA FOR A
 DWELLING AREA. EVERY DWELLING UNIT SHALL HAVE AT LEAST
 ONE ROOM THAT SHALL HAVE NOT LESS THAN 120 SQUARE FEET
 (13.9 M2) OF NET FLOOR AREA. OTHER HABITABLE ROOMS
 SHALL HAVE A NET FLOOR AREA OF NOT LESS THAN 70 SQUARE
 FEET (6.5 M2).
 LIVING ROOM AREA OF 94.95 SQ FT
 BEDROOM AREA OF 108.15 SQ FT
  
 5) 2ND REQUEST: SHEET # 1 ROOM # 4 AN EFFICIENCY UNIT
 WILL NEED TO MEET THE REQUIREMENT OF 2010 FBC-B 1208.4
 EFFICIENCY DWELLING UNITS. AN EFFICIENCY LIVING UNIT
 SHALL CONFORM TO THE REQUIREMENTS OF THE CODE EXCEPT AS
 MODIFIED HEREIN:
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
  
 6) SHEET # 1 INDICATES A ONE HOUR SEPERATION WALL
 BETWEEN UNITS, BUT NOT BETWEEN THE LAUNDRY ROOM AND
 UNIT #3. PLEASE REVIEW FBC-B CONTINUITY.
 709.4 CONTINUITY. SMOKE BARRIERS SHALL FORM AN
 EFFECTIVE MEMBRANE CONTINUOUS FROM OUTSIDE WALL TO
 OUTSIDE WALL AND FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, DECK OR SLAB ABOVE, INCLUDING
 CONTINUITY THROUGH CONCEALED SPACES, SUCH AS THOSE
 FOUND ABOVE SUSPENDED CEILINGS, AND INTERSTITIAL
 STRUCTURAL AND MECHANICAL SPACES. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL OR FLOOR SUPPORTED
 IN BUILDINGS OF OTHER THAN TYPE IIB, IIIB OR VB
 CONSTRUCTION.
 SEE EXCEPTION # 1 FOR REQUIRED 1 HR FIRE SEPERATION FOR
 CRAWL SPACES.
 4. THE FIRE PARTITION SEPARATING TENANT SPACES IN A
 MALL, COMPLYING WITH SECTION 402.7.2, ARE NOT REQUIRED
 TO EXTEND BEYOND THE UNDERSIDE OF A CEILING THAT IS NOT
 PART OF A FIRE-RESISTANCE-RATED ASSEMBLY. A WALL IS NOT
 REQUIRED IN ATTIC OR CEILING SPACES ABOVE TENANT
 SEPARATION WALLS.
  
 5. COMPLIED.
  
 6. FIREBLOCKING OR DRAFTSTOPPING IS NOT REQUIRED AT THE
 PARTITION LINE IN BUILDINGS EQUIPPED WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED THROUGHOUT IN ACCORDANCE
 WITH SECTION 903.3.1.1 OR 903.3.1.2, PROVIDED THAT
 AUTOMATIC SPRINKLERS ARE INSTALLED IN COMBUSTIBLE
 FLOOR/CEILING AND ROOF/CEILING SPACES.
  
 7) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION
 IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN
 OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN
 SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE
 FOLLOWING SHALL BE PROVIDED:
  
 709.4.1.1 ROOF SHEATHING. THE ROOF SHEATHING OR DECK
 SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIALS OR OF
 FIRE-RETARDANT-TREATED WOOD, FOR A DISTANCE OF 4 FEET
 (1220 MM); OR
  
 709.4.1.2 ROOF PROTECTION. THE ROOF SHALL BE PROTECTED
 WITH 0.625-INCH (15.88 MM) TYPE X GYPSUM BOARD DIRECTLY
 BENEATH THE UNDERSIDE OF THE ROOF SHEATHING OR DECK,
 SUPPORTED BY A MINIMUM OF NOMINAL 2-INCH (51 MM)
 LEDGERS ATTACHED TO THE SIDES OF THE ROOF FRAMING
 MEMBERS, FOR A MINIMUM DISTANCE OF 4 FEET (1220 MM).
  
 8) SEMI- COMPLIED, ELEVATIONS DO NOT INDICATE WHICH
 WINDOWS WILL BE INSTALLED WITH THE 45 MINUTE FIRE RATED
 WINDOWS.
 SHEET # 2 INDICATES ON THE RIGHT ELEVATION WINDOWS AND
 DOORS WITH IN 10'-0" OF THE EXTERIOR STAIR, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B:
 1026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. EXTERIOR
 EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1022.1.
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS
 FROM NORMALLY OCCUPIED SPACES.
 EXCEPTIONS:
 1.SEPARATION FROM THE INTERIOR OF THE BUILDING IS NOT
 REQUIRED FOR OCCUPANCIES, OTHER THAN THOSE IN GROUP R-1
 OR R-2, IN BUILDINGS THAT ARE NO MORE THAN TWO STORIES
 ABOVE GRADE PLANE WHERE THE LEVEL OF EXIT DISCHARGE IS
 THE FIRST STORY ABOVE GRADE PLANE.
  
 9) FIRES COMMENTS INDICATING THIS WAS A ROOMING HOUSE
 AND WILL NOW BE USED AS A APARTMENT BUILDING CREATES A
 CHANGE OF OCCUPANCY CLASSIFICATION 2010 EXIST BUILD
 CODE SECTION 901.3 THIS INCLUDES A CHANGE OF OCCUPANCY
 WITHIN THE SAME GROUP, ROOMING HOUSE TO APTARTMENTS.
  
 2010 EXIST BUILD CODE 904.1 FIRE PROTECTION
 REQUIREMENTS OF SECTION 912 SHALL APPLY WHERE A
 BUILDING OR PORTION OF BUILDING THERE OF UNDERGO A
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 2010 EXIST BUILD CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B 903.2.8 GROUP R. [F]
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL
 BUILDINGS WITH A GROUP R FIRE AREA.
 THE CODE COMMENTARY MAKES IT CLEAR THE ONLY EXCEPTION
 IS RESIDENTIAL UNITS THAT ARE COVERED UNDER THE FBC-R
 RESIDENTIAL CODE ONE AND TWO FAMILY RESIDENCES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER