| 2012-06-15 13:15:55 | 428 10TH STREET |
| | PERMIT #12060308 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: UPSTAIRS UNIT #5 AND UNIT #6 ARE INDICATED AS |
| | "EXISTING" ON THE PLANS WHILE UNIT #1-#4 ARE NOT |
| | INDICATED AS EXISTING AND THEREFORE WILL BE TREATED AS |
| | "NEW." |
| | |
| | NEW APARTMENTS ARE REQUIRED TO BE PROTECTED BY AN |
| | AUTOMATIC SUPERVISED FIRE SPRINKLER SYSTEM. |
| | |
| | PROVIDE A DETAIL FOR THE NEW FIRE-RATED WALLS. |
| | |
| | PROVIDE AN EXISTING FLOOR PLAN OR A DEMOLITION DRAWING |
| | TO SHOW CURRENT CONDITIONS. |
| | |
| | DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF |
| | BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED. ALL DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT |
| | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, |
| | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN |
| | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER |
| | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR |
| | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT |
| | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH |
| | DIAMETER SPHERE. |
| | |
| | FOR APARTMENTS WITH FOSSIL FUEL BURNING APPLIANCES, A |
| | CARBON MONOXIDE ALARM SHALL BE INSTALLED WITHIN 10 FEET |
| | OF EACH ROOM USED FOR SLEEPING PURPOSES. INDICATE THE |
| | POWER SOURCE FOR THE SMOKE AND CARBON MONOXIDE ALARMS. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |