| Plan Review Notes For Permit 12060308 |
| Permit Number |
12060308 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-15 11:46:02 | 12060405 | | | 428 10TH STREET | | | APARTMENT RENOVATIONS | | | | | | PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL SERVICE. | | | NEC 215.5, 220.40 | | | MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL | | | SERVICE IS LIMITED TO SIX SWITCHES GROUPED IN ONE | | | LOCATION. NEC 230.70 | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC | | | 110.9, 110.10 | | | SHOW LOCATION OF ALL ELECTRICAL PANELBOARDS. NEC 110.26 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. 2007 FBC R313 | | | GFCI PROTECTED OUTLETS UNIT ARE REQUIRED FOR EACH | | | DWELLING AT GRADE LEVEL AND ON BALCONIES. NEC 210.52(E) | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | | | | |
|