Plan Review Notes
Plan Review Notes For Permit 12060308
Permit Number 12060308
Review Stop E
Sequence Number 1
Notes
Date Text
2012-06-15 11:46:0212060405
 428 10TH STREET
 APARTMENT RENOVATIONS
  
 PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL SERVICE.
 NEC 215.5, 220.40
 MAXIMUM NUMBER OF DISCONNECTS FOR THE ELECTRICAL
 SERVICE IS LIMITED TO SIX SWITCHES GROUPED IN ONE
 LOCATION. NEC 230.70
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
 SHOW LOCATION OF ALL ELECTRICAL PANELBOARDS. NEC 110.26
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2007 FBC R313
 GFCI PROTECTED OUTLETS UNIT ARE REQUIRED FOR EACH
 DWELLING AT GRADE LEVEL AND ON BALCONIES. NEC 210.52(E)
  