| 2012-07-05 11:53:43 | BUILDING PLAN REVIEW |
| | PERMIT: 12060308 |
| | ADD: 428 10TH STREET (FRONT) |
| | CONT: RECORD CONSTRUCTION |
| | TEL: (561)662-2775 |
| | 2010 FLORIDA BUILDING CODE/ RESIDENTIAL W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, THE |
| | CONTRACTOR SUBMITTED PRODUCT APPROVALS FOR EXTERIOR |
| | DOORS AND MULLIONS BUT NO WINDOW APPROVALS |
| | WERE SUBMITTED WTIHIN THIS PERMIT PACKAGE. |
| | |
| | 2) 2010 WPB ADMINISTRATIVE CODE 107.3.4.1 DESIGN |
| | PROFESSIONALS SHALL REVIEW PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 , SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3) 2010 FBC-B 1209.2 ATTIC SPACES. AN OPENING NOT LESS |
| | THAN 20 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE |
| | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF |
| | OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM |
| | CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT |
| | OR ABOVE THE ACCESS OPENING. |
| | |
| | 4) SHEET # 1 ROOM # 3 DOES NOT MEET THE REQUIREMENTS OF |
| | 2010 FBC-B 1208.3 ROOM AREA. EVERY DWELLING UNIT SHALL |
| | HAVE AT LEAST ONE ROOM THAT SHALL HAVE NOT LESS THAN |
| | 120 SQUARE FEET (13.9 M2) OF NET FLOOR AREA. OTHER |
| | HABITABLE ROOMS SHALL HAVE A NET FLOOR AREA OF NOT LESS |
| | THAN 70 SQUARE FEET (6.5 M2). |
| | LIVING ROOM AREA OF 94.95 SQ FT |
| | BEDROOM AREA OF 108.15 SQ FT |
| | |
| | 5) SHEET # 1 ROOM # 4 AN EFFICIENCY UNIT WILL NEED TO |
| | MEET THE REQUIREMENT OF 2010 FBC-B 1208.4 EFFICIENCY |
| | DWELLING UNITS. AN EFFICIENCY LIVING UNIT SHALL CONFORM |
| | TO THE REQUIREMENTS OF THE CODE EXCEPT AS MODIFIED |
| | HEREIN: |
| | 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN |
| | 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL |
| | 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE |
| | PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF |
| | TWO. |
| | |
| | 6) SHEET # 1 INDICATES A ONE HOUR SEPERATION WALL |
| | BETWEEN UNITS, BUT NOT BETWEEN THE LAUNDRY ROOM AND |
| | UNIT #3. PLEASE REVIEW FBC-B CONTINUITY. |
| | 709.4 CONTINUITY. SMOKE BARRIERS SHALL FORM AN |
| | EFFECTIVE MEMBRANE CONTINUOUS FROM OUTSIDE WALL TO |
| | OUTSIDE WALL AND FROM THE TOP OF THE FOUNDATION OR |
| | FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE |
| | FLOOR OR ROOF SHEATHING, DECK OR SLAB ABOVE, INCLUDING |
| | CONTINUITY THROUGH CONCEALED SPACES, SUCH AS THOSE |
| | FOUND ABOVE SUSPENDED CEILINGS, AND INTERSTITIAL |
| | STRUCTURAL AND MECHANICAL SPACES. THE SUPPORTING |
| | CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED |
| | FIRE-RESISTANCE RATING OF THE WALL OR FLOOR SUPPORTED |
| | IN BUILDINGS OF OTHER THAN TYPE IIB, IIIB OR VB |
| | CONSTRUCTION. |
| | SEE EXCEPTION # 1 FOR REQUIRED 1 HR FIRE SEPERATION FOR |
| | CRAWL SPACES. |
| | 4. THE FIRE PARTITION SEPARATING TENANT SPACES IN A |
| | MALL, COMPLYING WITH SECTION 402.7.2, ARE NOT REQUIRED |
| | TO EXTEND BEYOND THE UNDERSIDE OF A CEILING THAT IS NOT |
| | PART OF A FIRE-RESISTANCE-RATED ASSEMBLY. A WALL IS NOT |
| | REQUIRED IN ATTIC OR CEILING SPACES ABOVE TENANT |
| | SEPARATION WALLS. |
| | |
| | 5. FIREBLOCKING OR DRAFTSTOPPING IS NOT REQUIRED AT THE |
| | PARTITION LINE IN GROUP R-2 BUILDINGS THAT DO NOT |
| | EXCEED FOUR STORIES IN HEIGHT, PROVIDED THE ATTIC SPACE |
| | IS SUBDIVIDED BY DRAFTSTOPPING INTO AREAS NOT EXCEEDING |
| | 3,000 SQUARE FEET (279 M2) OR ABOVE EVERY TWO DWELLING |
| | UNITS, WHICHEVER IS SMALLER. |
| | |
| | 6. FIREBLOCKING OR DRAFTSTOPPING IS NOT REQUIRED AT THE |
| | PARTITION LINE IN BUILDINGS EQUIPPED WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED THROUGHOUT IN ACCORDANCE |
| | WITH SECTION 903.3.1.1 OR 903.3.1.2, PROVIDED THAT |
| | AUTOMATIC SPRINKLERS ARE INSTALLED IN COMBUSTIBLE |
| | FLOOR/CEILING AND ROOF/CEILING SPACES. |
| | |
| | 7) 709.4.1 ROOF CONSTRUCTION. WHEN THE FIRE PARTITION |
| | IS CONTINUOUS TO THE UNDERSIDE OF THE ROOF SHEATHING IN |
| | OCCUPANCIES OF GROUPS R-1, R-2 AND R-3 AS APPLICABLE IN |
| | SECTION 101.2, IN TYPE III, IV AND V CONSTRUCTION THE |
| | FOLLOWING SHALL BE PROVIDED: |
| | |
| | 709.4.1.1 ROOF SHEATHING. THE ROOF SHEATHING OR DECK |
| | SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIALS OR OF |
| | FIRE-RETARDANT-TREATED WOOD, FOR A DISTANCE OF 4 FEET |
| | (1220 MM); OR |
| | |
| | 709.4.1.2 ROOF PROTECTION. THE ROOF SHALL BE PROTECTED |
| | WITH 0.625-INCH (15.88 MM) TYPE X GYPSUM BOARD DIRECTLY |
| | BENEATH THE UNDERSIDE OF THE ROOF SHEATHING OR DECK, |
| | SUPPORTED BY A MINIMUM OF NOMINAL 2-INCH (51 MM) |
| | LEDGERS ATTACHED TO THE SIDES OF THE ROOF FRAMING |
| | MEMBERS, FOR A MINIMUM DISTANCE OF 4 FEET (1220 MM). |
| | |
| | 8) SHEET # 2 INDICATES ON THE RIGHT ELEVATION WINDOWS |
| | AND DOORS WITH IN 10'-0" OF THE EXTERIOR STAIR, PLEASE |
| | PROVIDE COMPLIANCE WITH 2010 FBC-B: |
| | 1026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. EXTERIOR |
| | EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED FROM THE |
| | INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1022.1. |
| | OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS |
| | FROM NORMALLY OCCUPIED SPACES. |
| | EXCEPTIONS: |
| | 1. SEPARATION FROM THE INTERIOR OF THE BUILDING IS NOT |
| | REQUIRED FOR OCCUPANCIES, OTHER THAN THOSE IN GROUP R-1 |
| | OR R-2, IN BUILDINGS THAT ARE NO MORE THAN TWO STORIES |
| | ABOVE GRADE PLANE WHERE THE LEVEL OF EXIT DISCHARGE IS |
| | THE FIRST STORY ABOVE GRADE PLANE. |
| | |