Plan Review Notes
Plan Review Notes For Permit 12060295
Permit Number 12060295
Review Stop B
Sequence Number 1
Notes
Date Text
2012-06-14 10:59:24RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC
  
 1- FLAT ROOF ASSEMBLY:
 A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FROM NOA
 07-1219.09 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1219.09 SUBMITTED. NEED RAS 117 CALCULATIONS TO MEET
 THE DESIGN PRESSURES OF ROOF ZONES 2 AND 3 (PERIMETER
 AND CORNER AREAS). SEC. R301.2.1.4.3.
  
 NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON
 EXPOSURE "D".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712