| 2012-06-14 10:59:24 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FBC | | | | | | 1- FLAT ROOF ASSEMBLY: | | | A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FROM NOA | | | 07-1219.09 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES REQUIRED BY SEC. | | | R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE. | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 07-1219.09 SUBMITTED. NEED RAS 117 CALCULATIONS TO MEET | | | THE DESIGN PRESSURES OF ROOF ZONES 2 AND 3 (PERIMETER | | | AND CORNER AREAS). SEC. R301.2.1.4.3. | | | | | | NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON | | | EXPOSURE "D". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|