| Plan Review Notes For Permit 12060211 |
| Permit Number |
12060211 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-07-06 12:17:22 | 1601 FORUM PLACE - SUITE #805 | | | TRACKING #12060211 | | | MASTER #11110602 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENT: THE CONFERENCE ROOM (ASSEMBLY USE) | | | APPEARS TO BE APPROXIMATELY 800 SQ.FT. WHICH EQUATES TO | | | AN OCCUPANT LOAD OF 54 PERSONS BASED UPON 15 SQ.FT. PER | | | PERSON. THIS WOULD RESULT IN AN ASSEMBLY OCCUPANCY AND | | | NOT A BUSINESS OCCUPANCY WHEREBY THE LIFE SAFETY DESIGN | | | WOULD NEED TO MODIFIED TO ACCOMPANY THIS OCCUPANCY | | | TYPE. | | | | | | POSTING A MAXIMUM OCCUPANT LOAD SIGN WILL NOT SOLVE | | | THIS ISSUE AND WOULD BE VERY DIFFICULT TO | | | MONITOR/ENFORCE. THIS ROOM MAY BE USED BY ANOTHER | | | TENANT LONG AFTER THE CURRENT TENANT HAS VACATED. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|