Plan Review Notes
Plan Review Notes For Permit 12060211
Permit Number 12060211
Review Stop B
Sequence Number 2
Notes
Date Text
2012-07-06 08:20:53BUILDING PLAN REVIEW
 PERMIT: 12060211/ 11110602
 ADD: 1601 FORUM PL # 805
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE REVISION SHEET A-5 PLUMBING FIXTURES INDICATES
 IT IS DESIGNED TO THE 2010 FBC. THE 2010 FBC WAS
 ADOPTED STATEWIDE ON MARCH 15/ 2012, BUT THIS IS A
 PERMIT THAT WAS APPLIED FOR BEFORE THAT DATE KEEPING
 THE ASSOCIATED REVISIONS ALSO IN THE 2007 FBC.
  
 2) COMPLIED. 28 OCCUPANTS.
  
 3) COMPLIED. 28 OCCUPANTS.
  
 4) THIS REVISION IS TO BE REVIEWED UNDER THE 2007 FBC
 CHAPTER 11 ACCESSIBILITY CODE. SECTION 11-4.1.3(11) IF
 TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON
 USE TOILET ROOMS SHALL COMPLY WITH SECTION 11-4.22(
 TOLIET ROOMS). OTHER TOILET ROOMS PROVIDED FOR THE USE
 OF OCCUPANTS OF SPECIFIC SPACES (I.E., A PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE OFFICE) SHALL BE
 ADAPTABLE.
 1-4.22.2 DOORS.
  
 11-4.22.2 (1) ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 11-4.22.3 CLEAR FLOOR SPACE. THE ACCESSIBLE FIXTURES
 AND CONTROLS REQUIRED IN SECTIONS 11-4.22.4, 11-4.22.5,
 11-4.22.6 AND 11-4.22.7 SHALL BE ON AN ACCESSIBLE
 ROUTE. AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH
 SECTION 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE
 TOILET ROOM. THE CLEAR FLOOR SPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE TURNING SPACE
 MAY OVERLAP.
  
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER
 CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL
 COMPLY WITH SECTION 11-4.16.
  
 11-4.22.5 URINALS. IF URINALS ARE PROVIDED, THEN AT
 LEAST ONE SHALL COMPLY WITH SECTION 11-4.18.
  
 11-4.22.6 LAVATORIES AND MIRRORS. IF LAVATORIES AND
 MIRRORS ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL
 COMPLY WITH SECTION 11-4.19.
  
 11-4.22.7 CONTROLS AND DISPENSERS. IF CONTROLS,
 DISPENSERS, RECEPTACLES, OR OTHER EQUIPMENT ARE
 PROVIDED, THEN AT LEAST ONE OF EACH SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL COMPLY WITH SECTION 11-4.27.
  
 5) INFORMATIONAL ONLY. 2007 VS 2010 INTHE 2010 FBC
 ACCESSIBILITY THE MINIMUM NUMBER OF DRINKING FOUNTAINS
 IS (2) 602.4 FOR WHEELCHAIR BOUND AND 602.7 DRINKING
 FOUNTAINS FOR STANDING PERSONS.
  
 6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]