| 2012-06-14 14:23:08 | BUILDING PLAN REVIEW |
| | PERMIT: 12060211/ 11110602 |
| | ADD: 1601 FORUM PL # 805 |
| | CONT: ANDERSON MOORE |
| | TEL: (561)662-1819 |
| | |
| | 2007 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE REVISION THAT WAS SUBMITTED INDICATES IT IS |
| | DESIGNED TO THE 2010 FBC. THE 2010 FBC WAS ADOPTED |
| | STATEWIDE ON MARCH 15/ 2012, BUT THIS IS A PERMIT THAT |
| | WAS ISSUED BEFORE THAT DATE KEEPING THE ASSOCIATED |
| | REVISIONS ALSO IN THE 2007 FBC. |
| | |
| | 2) THE CONFERENCE ROOM IS OVER 750 SQ FT, MAKING IT A |
| | ACCESORY OCCUPANCY (ASSEMBLY A-3) THIS WILL REQUIRE A |
| | RATED CORRIDOR SEE 2007 FBC-BTABLE 1017.1. |
| | |
| | 3) WITH THE OCCUPANT LOAD OF THE CONFERENCE ROOM OVER |
| | 50 WHEN FIGURED AT 15 SQ FT PER OCCUPANT 2007 FBC-B |
| | TABLE 1019.2 WOULD REQUIRE 2 DOORS. |
| | |
| | 4) 2007 VS 2010 FBC IN THE 2010 FBC- ACCESSIBILITY THE |
| | PRIVATE OFFICES CAN ONLY OCCUR WHEN GOING THROUGH A |
| | PRIVATE OFFICE, ACCESSIBILTY 604.4 EXCEPTION# 1. |
| | WITHIN THE 2007 CODE THE LANGUAGE IS NOT AS STRICT HOW, |
| | OR WHO WILL BE USING THESE RESTROOMS AS PRIVATE |
| | RESTROOMS 11-4.1.3(11). |
| | |
| | 5) 2007 VS 2010 INTHE 2010 FBC ACCESSIBILITY THE |
| | MINIMUM NUMBER OF DRINKING FOUNTAINS IS (2) 602.4 FOR |
| | WHEELCHAIR BOUND AND 602.7 DRINKING FOUNTAINS FOR |
| | STANDING PERSONS. |
| | |
| | 6) PLEASE PROVIDE COMPLIANCE WITH 2007 FBC-B 11-4.31, |
| | TELEPHONES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |