| Plan Review Notes For Permit 12060193 |
| Permit Number |
12060193 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-09 20:34:03 | 303 BANYAN BOULEVARD - 3RD FLOOR LOBBY | | | PERMIT #12060193 | | | MASTER #12050115 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO- SUBMIT REVISION BEFORE FINAL FIRE | | | INSPECTION***** | | | | | | SPRINKLERS LOCATED IN THE 10'-6" CEILING HAVE THEIR | | | SPRAY OBSTRUCTED BY THE 9'-6" SOFFIT. PROVIDE | | | ADDITIONAL SPRINKLERS IN SOFFIT AREA OR RELOCATE | | | CEILING SPRINKLERS TO SOFFIT. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|