| 2012-06-29 15:50:09 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER (CARL A. WILSON) TO SIGN AND SEAL DRAWINGS |
| | AS REQUIRED BY FLORIDA STATUTE 471 WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 AND 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 3- ENGINEER TO PROVIDE ALL THE DESIGN PARAMETERS |
| | INFORMATION ON THE PLANS. SPECIFY CURRENT CODE IN |
| | EFFECT, SPECIFY THE BUILDING EXPOSURE, SPECIFY THE |
| | ULTIMATE AND NOMINAL WIND LOADS. AND SPECIFY THE DESIGN |
| | PRESSURES FOR DOORS AND WINDOWS INCLUDING THE GARAGE |
| | DOOR. SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | NOTE: ACCORDING TO SEC. R301.2.1.4.3, THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C", |
| | |
| | 4- COLUMN ELEVATION DETAIL: ENGINEER TO CLARIFY HOW IS |
| | THE STEEL COLUMN GOING TO BE FASTENED AT THE BASE. |
| | PROVIDE COMPLETE SPECIFICATIONS FOR COLUMN BASE AND |
| | CLARIFY WHY ONLY ONE 3/8" DIA. ANCHOR WAS SPECIFIED. |
| | HOW MUCH ANCHOR EMBEDMENT IS REQUIRED INTO THE CONCRETE |
| | FOOTING?. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 5- PROVIDE MANUFACTURER SPECIFICATIONS FOR DOORS AND |
| | WINDOWS SHOWING COMPLIANCE WITH THE ENERGY EFFICIENCY |
| | REQUIRED BY THE ENERGY CALCULATIONS AND TABLE 402.1.1 |
| | OF THE 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES). SEC. 107.2 CITY |
| | AMENDMENTS TO FBC: |
| | A) GARAGE DOOR. NOA 09-0604.03 SUBMITTED WAS SUPERSEDED |
| | BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE AND |
| | DOWNLOAD CURRENT NOA. |
| | |
| | B) SINGLE HUNG WINDOWS. NOA 11-0705.09 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. DOWNLOAD CURRENT NOA. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR STORM |
| | SHUTTERS INSTALLATION. CLEARLY IDENTIFY SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE |
| | USED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | [email protected] |