| 2012-07-05 16:56:02 | BUILDING PLAN REVIEW |
| | PERMIT: 12060134 |
| | ADD: 427 SUMMA ST |
| | CONT: O/B VIGHETTO, EDWARD |
| | TEL: (561)379-5733 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE HOW MANY IF ANY CHILDREN ARE |
| | INCAPABLE OF SELF- PRESERVATION? 313.2 |
| | SUB-CLASSIFICATION? |
| | |
| | 2) 436.10.5 SMOKE DETECTION SYSTEMS. |
| | |
| | 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN |
| | ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT |
| | REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED |
| | WITHIN DAY CARE HOMES. |
| | |
| | EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN |
| | ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE |
| | SAME MANNER SHALL BE PERMITTED. |
| | |
| | 436.10.5.2 NOT APPLICABLE. |
| | |
| | 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED |
| | BY THE BUILDING ELECTRICAL SYSTEM. |
| | |
| | 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE |
| | PROVIDED IN ALL ROOMS USED FOR SLEEPING. |
| | |
| | 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED |
| | WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA, |
| | THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE |
| | ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING |
| | UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND. |
| | |
| | 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN |
| | INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA |
| | AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM. |
| | REMOTE ANNUNCIATION SHALL BE PERMITTED. |
| | |
| | 3) 1034.6 SPECIAL MEANS OF EGRESS FEATURES. EVERY ROOM |
| | OR SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER |
| | THAN BATHROOMS, SHALL HAVE AT LEAST ONE OUTSIDE WINDOW |
| | FOR EMERGENCY RESCUE AND VENTILATION. SUCH WINDOW SHALL |
| | BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF TOOLS |
| | AND SHALL PROVIDE A CLEAR OPENING OF NOT LESS THAN 20 |
| | INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT, |
| | AND 5.7 SQUARE FEET (0.53 M2) IN AREA. THE BOTTOM OF |
| | THE OPENING SHALL BE NOT MORE THAN 44 INCHES (1118 MM) |
| | ABOVE THE FLOOR. THE CLEAR OPENING SHALL PERMIT A |
| | RECTANGULAR SOLID, WITH A MINIMUM WIDTH AND HEIGHT THAT |
| | PROVIDES THE REQUIRED 5.7 SQUARE FOOT (0.53 M2) OPENING |
| | AND A MINIMUM DEPTH OF 20 INCHES (8 MM), TO PASS FULLY |
| | THROUGH THE OPENING. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2012-06-08 07:48:29 | 6/8 ASSIGNED TO B10 |
| | |
| | |