Plan Review Notes
Plan Review Notes For Permit 12060134
Permit Number 12060134
Review Stop B
Sequence Number 1
Notes
Date Text
2012-07-05 16:56:02BUILDING PLAN REVIEW
 PERMIT: 12060134
 ADD: 427 SUMMA ST
 CONT: O/B VIGHETTO, EDWARD
 TEL: (561)379-5733
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE HOW MANY IF ANY CHILDREN ARE
 INCAPABLE OF SELF- PRESERVATION? 313.2
 SUB-CLASSIFICATION?
  
 2) 436.10.5 SMOKE DETECTION SYSTEMS.
  
 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN
 ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT
 REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED
 WITHIN DAY CARE HOMES.
  
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
  
 436.10.5.2 NOT APPLICABLE.
  
 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED
 BY THE BUILDING ELECTRICAL SYSTEM.
  
 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE
 PROVIDED IN ALL ROOMS USED FOR SLEEPING.
  
 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED
 WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA,
 THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE
 ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING
 UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
  
 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN
 INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA
 AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
 REMOTE ANNUNCIATION SHALL BE PERMITTED.
  
 3) 1034.6 SPECIAL MEANS OF EGRESS FEATURES. EVERY ROOM
 OR SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER
 THAN BATHROOMS, SHALL HAVE AT LEAST ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE AND VENTILATION. SUCH WINDOW SHALL
 BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF TOOLS
 AND SHALL PROVIDE A CLEAR OPENING OF NOT LESS THAN 20
 INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT,
 AND 5.7 SQUARE FEET (0.53 M2) IN AREA. THE BOTTOM OF
 THE OPENING SHALL BE NOT MORE THAN 44 INCHES (1118 MM)
 ABOVE THE FLOOR. THE CLEAR OPENING SHALL PERMIT A
 RECTANGULAR SOLID, WITH A MINIMUM WIDTH AND HEIGHT THAT
 PROVIDES THE REQUIRED 5.7 SQUARE FOOT (0.53 M2) OPENING
 AND A MINIMUM DEPTH OF 20 INCHES (8 MM), TO PASS FULLY
 THROUGH THE OPENING.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  