| 2012-08-03 15:25:23 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | |
| | 1- ENERGY CALCULATIONS CALL FOR WOOD DOORS. PRODUCT |
| | APPROVAL SUBMITTED ARE NOT FOR WOOD DOORS. REVISE AS |
| | REQUIRED. ALSO. MATCH NUMBER OF DOORS AS SHOWN ON |
| | PLANS. REVISE ENERGY CALCULATIONS AS REQUIRED. |
| | 2- CLEARLY IDENTIFY SPECIFIC WINDOW MULLION SIZE ON NOA |
| | SUBMITTED TO VERIFY COMPLIANCE WITH THE CALCULATED |
| | DESIGN PRESSURES. |
| | 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE ELEVATOR |
| | SHOWING COMPLIANCE WITH ASME A17.1 AS REQUIRED BY SEC. |
| | R321. |
| | 4- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| | CONSTRUCTION AND INSTALLATION OF THE STAIRS, HANDRAILS |
| | AND GUARDRAILS AND THE BALCONY GUARDRAILS. SEE TABLE |
| | R301.5 |
| | 5- SEALOFLEX WATERPROOFING FOR BALCONY DECK. CLEARLY |
| | SPECIFY APPROVED ASSEMBLY TO BE USED AND PROVIDE THE |
| | SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY |
| | GENERAL LIMITATION #7. |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) FLAT ROOF ASSEMBLY. AND, CLEARLY IDENTIFY APPROVED |
| | ASSEMBLY TO BE INSTALLED. AND, PROVIDE THE RAS 117 |
| | CALCULATIONS AS REQUIRED. IF PRODUCT APPROVAL REQUIRES |
| | SIGNED AND SEALED RAS117 CALCULATIONS, THEN PROVIDE |
| | THEM. |
| | B) GARAGE DOOR SIZE AS SHOWN ON PLANS. |
| | C) METAL ROOFING AS SPECIFIED ON PLANS. NOA 07-1025.04 |
| | SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED CURRENT |
| | ONE. |
| | 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |