2012-06-20 16:50:381. PROVIDE HEAT LOADS, FBC R 103.2.1, ENERGY CALCS.
  
 2. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD
 ZONE. ELEVATION OF MECHANICAL EQUIPMENT IS TO BE 6"
 ABOVE BFE. SHOW PROPOSED HEIGHT ON PLAN. THIS SHOULD
 ALSO BE INCLUDED ON ELEVATION CERTIFICATE, CONSTRUCTION
 DRAWINGS, WPB ADMIN CODE 94-546(B).
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR