2012-06-25 15:56:20RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- A) HOUSE IS LOCATED ON FLOOD ZONE A5 (EL. 7').
 ACCORDING TO SURVEY SUBMITTED THE FINISHED FLOOR
 ELEVATION OF THIS HOUSE IS 7.35'. THE HOUSE NEEDS TO BE
 RAISED TO A MINIMUM FINISHED FLOOR ELEVATION OF 7.5'.
 AND, IF THE GARAGE FINISHED FLOOR IS BELOW 7.5', THEN
 FLOOD VENTS ARE REQUIRED IN THE GARAGE. ARTICLE XVII OF
 CITY OF WEST PALM BEACH FLOOD PREVENTION AND CONTROL
 SECTIONS 94-541 THRU 94-547. REVISE PLANS SHOWING
 COMPLIANCE WITH THE MINIMUM REQUIRED FINISH FLOOR
 ELEVATION. SURVEY, WILL BE REQUIRED DURING CONSTRUCTION
 TO DEMONSTRATE ELEVATED FINISH FLOOR ELEVATION.
  
 B) NOTE #9 OF SURVEY SUBMITTED SPECIFIES THAT THIS
 SURVEY IS NOT TO BE USED FOR CONSTRUCTION PURPOSES.
 REVISE AS REQUIRED.
  
 C) SURVEY NEEDS TO HAVE SURVEYOR'S ORGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SECTIONS
 101.4.3, 103.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- ACCORDING TO SEC. R301.2.1.4.3 OF 2010 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "D" NOT "C". REVISE THE DESIGN INFORMATION ON A5 AS
 REQUIRED.
  
 4- SPECIFY THE DESIGN PRESSURES FOR ALL WINDOWS AND
 DOORS AS REQUIRED BY SEC. R301.2.1.4.3. COORDINATE WITH
 ITEM 3 ABOVE.
  
 5- PROVIDE SOIL TEST REPORT TO SHOW COMPLIANCE WITH THE
 PROPOSED ADDITIONAL LOAD. SEC. R401.4.
  
 6- CLEARLY IDENTIFY SPECIFIC SIZE AND GLAZING TYPE ON
 NOA'S SUBMITTED FOR DOORS AND WINDOWS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED ON ITEM
 #4 ABOVE. SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 7- A) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE ELEVATOR HOISTWAY TO SUPPORT THE
 ELEVATOR. SEC. 107.2.1.3 CITY AMENDMENTS. COORDINATE
 WITH ITEM 7(B) BELOW.
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE ELEVATOR
 SHOWING COMPLIANCE WITH ASME A17.1 AS REQUIRED BY SEC.
 R321.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS ON THE
 PLANS FOR THE CONSTRUCTION AND INSTALLATION OF THE
 STAIRS, HANDRAILS AND GUARDRAILS AND THE BALCONY
 GUARDRAILS. SHOW LOCATION OF HANDRAILS ON STAIRWAY,
 RAILINGS AND GUARDRAILS HEIGHT, SPACING BETWEEN
 PICKETS. SEC. R312. AND, SHOW CONSTRUCTION TO MEET THE
 REQUIRED DESIGN LOADS OF TABLE R301.5
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) SEALOFLEX WATERPROOFING FOR BALCONY DECK DESIGNED TO
 RECEIVE TILE AS SPECIFIED ON PLANS. CLEARLY SPECIFY
 APPROVED ASSEMBLY TO BE USED AND PROVIDE THE SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/DETAILS. PROVIDE THE COVER PAGE AND PAGE SHOWING
 THE CONNECTOR ONLY. OR SPECIFY PRODUCT APPROVAL NUMBER
 ON PLANS. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
  
 D) FLAT ROOF ASSEMBLY. AND CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE THE RAS 117
 CALCULATIONS AS REQUIRED. IF PRODUCT APPROVAL REQUIRES
 SIGNED AND SEALED RAS117 CALCULATIONS, THEN PROVIDE
 THEM.
  
 E) GARAGE DOOR AS SHOWN ON PLANS.
  
 F) METAL ROOFING AS SPECIFIED ON PLANS.
  
 10- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- PROVIDE MANUFACTURER'S SPECS FOR SPRAY INSULATION
 TO BE USED TO VERIFY COMPLIANCE WITH SEC. R316, ALSO,
 NEED TO VERIFY REQUIRED THICKNESS TO MEET THE MINIMUM R
 VALUE REQUIRED BY THE ENERGY CALCULATIONS AND TABLE
 402.1.1 OF 2010 FBC-ENERGY CONSERVATION. THIS INCLUDES
 FLAT ROOF ABOVE STUDIO (CHECK ROOF RAFTERS SIZE).
  
 12- SPECIFY WALL SECTIONS THE MINIMUM R VALUE REQUIRED
 BY THE ENERGY CALCULATIONS AND TABLE 404.1.1 FOR WALLS
 (MASONRY AND WOOD FRAMED) AND CEILINGS.
  
 13- SPECIFY ON WALL SECTIONS:
 A) THE TWO LAYERS OF WATER RESISTANT BARRIER AS
 REQUIRED BY SEC. R703.6.3.
  
 B) 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1).
  
 14- PROVIDE SPECIFICATIONS FOR THE DOORS AND WINDOWS
 SHOWING COMPLIANCE WITH THE GLASS TYPE REQUIRED BY THE
 ENERGY CALCULATIONS AND TABLE 402.1.1.
  
 15- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315.
  
 16- SPECIFY ON PLANS DWELLING/GARAGE SEPARATION AS
 REQUIRED BY TABLE R302.6.
  
 17- PROVIDE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE
 FIREBLOCKING AS REQUIRED BY SEC. R302.11. INCLUDING
 CONCEALED SPACES, STAIRS, ELEVATOR SHAFT, ETC.
  
 18- SPECIFY ON PLANS ATTIC ACCESS AS REQUIRED BY SEC.
 R807.
  
 19- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 20- SHEET A5:
 A) FLOOR FRAMING PLAN SHOWS NEW 2X4 BEARING WALLS BY
 THE NEW STAIRWAY. FOUNDATION PLAN DOESN'T SHOW ANY
 FOOTING FOR THESE NEW BEARING WALLS. PROVIDE
 INFORMATION SHOWING HOW THE LOADS ARE TRANSFERED TO THE
 FOOTING AS REQUIRED BY SEC. R301.1.
  
 B) REVISED NOTE #5. MIN. 8D RING SHANK NAILS ARE
 REQUIRED (NOT 8D COMMON NAILS) BY SEC. R803.2.3.1 FOR
 ALL ROOF ZONES. ALSO, SPECIFY NAILS AT 4" O.C. FOR ZONE
 #3 (4'-0" WIDE MIN.)
  
 C) REVISE DESIGN LOADS AND WIND DESIGN INFORMATION.
 COORDINATE WITH ITEM #3 ABOVE.
  
 21- SHEET A10: PROVIDE COMPLETE SPECIFICATIONS ON
 DETAIL 9/A10. NO INFORMATION SUBMITTED. SEC. 107
 107.2.1 CITY AMENDMENTS TO FBC.
  