| 2012-06-27 11:00:36 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE |
| | REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF THE PROJECT. CITY AMENDMENTS 107.3.4.1 |
| | |
| | 2) THE PRODUCT APPROVALS FOR THE CONSTRUCTION GLASS |
| | INDUSTRIES SERIES '450' OUT-SWING ALUMINUM DOOR NOA NO. |
| | 06-0127.02 IS EXPIRED. PLEASE SUBMIT CURRENT PRODUCT |
| | APPROVALS. DCA RULE 9N-3 |
| | |
| | 3) THE PRODUCT APPROVALS FOR THE BIRDVIEW SKYLIGHTS NOA |
| | NO. 08-0611.09 HAS BEEN SUPERSEDED. PLEASE SUBMIT |
| | CURRENT PRODUCT APPROVALS. DCA RULE 9N-3 |
| | |
| | 4) SHOW THE LOCATIONS AND SIZE OF THE NEW SKYLIGHTS ON |
| | THE REAR ELEVATION AND SPECIFY THE REQUIRED WIND LOAD |
| | PRESSURES FOR THEM ON THE PLANS. FBC R301.2.1 |
| | |
| | 5) PROVIDE A DETAIL OF THE SKYLIGHT CONSTRUCTION. |
| | INCLUDE FRAMING, FINISH AND INSULATION INFORMATION ON |
| | THE DETAIL. CITY AMENDMENTS 107.2.1.3 |
| | |
| | 5) SPECIFY THE SIZE OF THE SLIDING GLASS DOOR AND THE |
| | REQUIRED WIND LOAD PRESSURES FOR THEM ON THE PLANS. FBC |
| | R301.2.1 |
| | |
| | 6) SPECIFY THE ACTUAL DOOR AND SIDELITE SIZES FOR THE |
| | FRONT AND REAR DOORS ON THE PLANS. CITY AMENDMENTS |
| | 107.2.1.3 |
| | |
| | 7) FROM THE SCALE ON THE PLANS IT APPEARS THAT THE |
| | FRONT DOOR IS 4' WIDE AND 8' IN HEIGHT. THE PRODUCT |
| | APPROVAL HAS A MAXIMUM WIDTH OF 3' FOR DOORS 8' IN |
| | HEIGHT AND 3' 6" FOR DOORS UP TO 7' 6" IN HEIGHT. |
| | PLEASE PROVIDE PRODUCT APPROVALS FOR THESE LARGER |
| | DOORS. DCA RULE 9N-3 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |