| Plan Review Notes For Permit 12060116 |
| Permit Number |
12060116 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-07-14 18:08:34 | 5840 CORPORATE WAY - SUITE #200 | | | PERMIT #12060116 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION WITH THE FOLLOWING | | | INFORMATION***** | | | | | | THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON | | | THE PLANS. | | | | | | FOR ADDRESSABLE SYSTEMS, INDICATE THE ADDRESS | | | (NUMBER/LETTER) OF EACH FIRE ALARM DEVICE ON THE | | | SYSTEM. | | | | | | INDICATE THE CIRCUIT CLASS. | | | | | | INDICATE THE CORRECT CANDELA OF THE VISUAL NOTIFICATION | | | APPLIANCES. CURRENTLY ALL DEVICES ARE INDICATED AS 15 | | | CD. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE |
|