2012-07-14 18:08:345840 CORPORATE WAY - SUITE #200
 PERMIT #12060116
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION WITH THE FOLLOWING
 INFORMATION*****
  
 THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON
 THE PLANS.
  
 FOR ADDRESSABLE SYSTEMS, INDICATE THE ADDRESS
 (NUMBER/LETTER) OF EACH FIRE ALARM DEVICE ON THE
 SYSTEM.
  
 INDICATE THE CIRCUIT CLASS.
  
 INDICATE THE CORRECT CANDELA OF THE VISUAL NOTIFICATION
 APPLIANCES. CURRENTLY ALL DEVICES ARE INDICATED AS 15
 CD.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE