2012-06-09 19:05:045840 CORPORATE WAY - SUITE #200
 PERMIT #12060116
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM PLANS ARE REQUIRED TO BE SEALED BY A
 PROFESSIONAL ENGINEER WHEN THE FIRE ALARM JOB VALUE
 EXCEEDS $5,000.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS
 TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
 PROVIDE A RISER DIAGRAM AND INDICATE THE WIRE SIZING
 AND CLASS.
  
 PROVIDE A SCALABLE FLOOR PLAN AND INDICATE THE ROOM USE
 OR NAME ON THE PLANS.
  
 INDICATE THE CANDELA OF THE VISUAL NOTIFICATION
 APPLIANCES.
  
 WORK TO BE DONE IN SUITE #100 IS NOT SHOWN ON THE PLANS
 OR INDICATED ON THE PERMIT APPLICATION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  