| Plan Review Notes For Permit 12060116 |
| Permit Number |
12060116 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-09 19:05:04 | 5840 CORPORATE WAY - SUITE #200 | | | PERMIT #12060116 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE ALARM PLANS ARE REQUIRED TO BE SEALED BY A | | | PROFESSIONAL ENGINEER WHEN THE FIRE ALARM JOB VALUE | | | EXCEEDS $5,000. | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS | | | TO EACH FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | PROVIDE A RISER DIAGRAM AND INDICATE THE WIRE SIZING | | | AND CLASS. | | | | | | PROVIDE A SCALABLE FLOOR PLAN AND INDICATE THE ROOM USE | | | OR NAME ON THE PLANS. | | | | | | INDICATE THE CANDELA OF THE VISUAL NOTIFICATION | | | APPLIANCES. | | | | | | WORK TO BE DONE IN SUITE #100 IS NOT SHOWN ON THE PLANS | | | OR INDICATED ON THE PERMIT APPLICATION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|