| Plan Review Notes For Permit 12060116 |
| Permit Number |
12060116 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-13 11:30:58 | PROVIDE CONDUCTOR SIZES AND TYPES AND CANDELA | | | RATINGSFOR STROBES. | | | INDICATE THE LOCATION OF THE FIRE ALARM CONTROL UNIT | | | AND POWER SUPPLY. | | | | | | 2010 FBC 907.1.1 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|