Plan Review Notes For Permit 12060109
Permit Number 12060109
Review Stop P
Sequence Number 2
Notes
Date Text
2012-08-13 11:20:04FBC PLUMBING 2010
 FBC ACCESSIBILITY 2010
 EXISTING BUILDING CODE 2010 REVIEW #2
 DENIED:
  
  
 1.FBC 2010 EXISTING BUILDING CODE 912.8
 SHEET A-0 SHOWS OCCUPANCY TYPE AS RESTURANT (A-2) WITH
 214 OCCUPANTS. 2 WATER CLOSETS WILL BE REQUIRED FOR
 WOMEN.
 WITH THE CHANGE OF OCCUPANCY IN THE NEW RESTURANT AREA
 THE RESTROOM WILL BE REQUIRED TO MEET THE 2010
 ACCESSIBILITY CODE.
  
 2. THE WOMENS RESTROOM IN THE NEW SECTION WILL BE
 REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIVE THE
 REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET.
 FBC ACCESSIBILITY CODE 2010 604.3.1 THE LAVATORY THAT
 IS IN THE SAME ROOM WILL NOT BE PERMITTED TO BE IN THE
 5' CLEAR SPACE.
 FBC ACCESSIBILITY CODE 2010 604.3.2
  
  