| Plan Review Notes For Permit 12060109 |
| Permit Number |
12060109 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-08-13 11:20:04 | FBC PLUMBING 2010 | | | FBC ACCESSIBILITY 2010 | | | EXISTING BUILDING CODE 2010 REVIEW #2 | | | DENIED: | | | | | | | | | 1.FBC 2010 EXISTING BUILDING CODE 912.8 | | | SHEET A-0 SHOWS OCCUPANCY TYPE AS RESTURANT (A-2) WITH | | | 214 OCCUPANTS. 2 WATER CLOSETS WILL BE REQUIRED FOR | | | WOMEN. | | | WITH THE CHANGE OF OCCUPANCY IN THE NEW RESTURANT AREA | | | THE RESTROOM WILL BE REQUIRED TO MEET THE 2010 | | | ACCESSIBILITY CODE. | | | | | | 2. THE WOMENS RESTROOM IN THE NEW SECTION WILL BE | | | REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIVE THE | | | REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET. | | | FBC ACCESSIBILITY CODE 2010 604.3.1 THE LAVATORY THAT | | | IS IN THE SAME ROOM WILL NOT BE PERMITTED TO BE IN THE | | | 5' CLEAR SPACE. | | | FBC ACCESSIBILITY CODE 2010 604.3.2 | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|