2012-06-12 12:33:145335 NORTH MILITARY TRAIL - SUITE #28
 PERMIT #12060109
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE CURRENT OCCUPANT LOAD ON FILE WITH THE FIRE
 DEPARTMENT IS 96 PERSONS. THE OCCUPANT LOAD STATED ON
 SHEET A-0 INDICATES 162 PERSONS. PROVIDE A DETAILED
 OCCUPANT LOAD CALCULATION FOR SPACES. FOR EXAMPLE, THE
 DANCE FLOOR AREA NEEDS TO BE FIGURED AT 7 SQ.FT. PER
 PERSON WHILE THE DINING AREAS WITH TABLES/TABLES WOULD
 BE FIGURED AT 15 SQ.FT. PERSON. ETC.
  
 SHEET A-0 INDICATES THERE IS NO EXISTING SPRINKLER
 SYSTEM. AN AUTOMATIC SPRINKLER SYSTEM IS REQUIRED FOR
 ASSEMBLY OCCUPANCIES WITH MORE THAN 100 PERSONS.
  
 PROVIDE CONSTRUCTION INFORMATION AND DETAILS FOR THE
 STAGE.
  
 NO INTERIOR WALL OR CEILING FINISH INFORMATION
 PROVIDED.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 INDICATE THE SCOPE OF WORK FOR THE FIRE ALARM SYSTEM.
 PLANS ONLY SHOW TWO FIRE ALARM HORN-STROBE DEVICES.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  