| 2012-06-12 12:33:14 | 5335 NORTH MILITARY TRAIL - SUITE #28 |
| | PERMIT #12060109 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE CURRENT OCCUPANT LOAD ON FILE WITH THE FIRE |
| | DEPARTMENT IS 96 PERSONS. THE OCCUPANT LOAD STATED ON |
| | SHEET A-0 INDICATES 162 PERSONS. PROVIDE A DETAILED |
| | OCCUPANT LOAD CALCULATION FOR SPACES. FOR EXAMPLE, THE |
| | DANCE FLOOR AREA NEEDS TO BE FIGURED AT 7 SQ.FT. PER |
| | PERSON WHILE THE DINING AREAS WITH TABLES/TABLES WOULD |
| | BE FIGURED AT 15 SQ.FT. PERSON. ETC. |
| | |
| | SHEET A-0 INDICATES THERE IS NO EXISTING SPRINKLER |
| | SYSTEM. AN AUTOMATIC SPRINKLER SYSTEM IS REQUIRED FOR |
| | ASSEMBLY OCCUPANCIES WITH MORE THAN 100 PERSONS. |
| | |
| | PROVIDE CONSTRUCTION INFORMATION AND DETAILS FOR THE |
| | STAGE. |
| | |
| | NO INTERIOR WALL OR CEILING FINISH INFORMATION |
| | PROVIDED. |
| | |
| | FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 |
| | OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON |
| | DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| | PANIC HARDWARE. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | INDICATE THE SCOPE OF WORK FOR THE FIRE ALARM SYSTEM. |
| | PLANS ONLY SHOW TWO FIRE ALARM HORN-STROBE DEVICES. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |