Plan Review Notes
Plan Review Notes For Permit 12060014
Permit Number 12060014
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-06-18 13:45:321889 PALM BEACH LAKES BOULEVARD
 PERMIT #12060014
 MASTER #12030394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS
 TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
  
 NOTE:
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW