| Plan Review Notes For Permit 12060014 |
| Permit Number |
12060014 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-18 13:45:32 | 1889 PALM BEACH LAKES BOULEVARD | | | PERMIT #12060014 | | | MASTER #12030394 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION***** | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS | | | TO EACH FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | | | | NOTE: | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|