| Plan Review Notes For Permit 12050856 |
| Permit Number |
12050856 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-02 16:54:49 | RESIDENTIAL (R3) REPAIRS, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- OWNER STATED THAT FRAMING FOR FRONT WINDOWS NEED TO | | | BE REBUILT. PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR | | | FRAMING AT FRONT WINDOWS. SPECIFY NUMBER/SIZE OF STUDS | | | AND HEADER SIZE. ALSO, SPECIFY ALL STRUCTURAL | | | CONNECTORS. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. | | | | | | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 OF CITY AMENDMENTS TO FBC FOR: | | | A) DOORS TO BE REPLACED AS SPECIFIED ON PLANS. NONE | | | SUBMITTED AT THIS TIME. | | | | | | B) WINDOW MULLIONS AS SHOWN ON ELEVATIONS SUBMITTED. | | | NONE SUBMITTED AT THIS TIME. | | | | | | C) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND | | | DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE | | | AND PAGE SHOWING THE STRUCTURAL CONNECTOR. | | | | | | 3- ARCHITECT OF RECORD TO REVIEW AN APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3..4.1 CITY AMENDMENTS TO FBC. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | 2012-06-21 14:58:33 | TO R3 |
|