| 2012-06-14 13:46:49 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE GENERAL NOTES ON SHEET A1 AND THE STRUCTURAL |
| | NOTES ON A4 SPECIFY THE 2007 FBC. THE 2010 FBC WENT |
| | INTO EFFECT ON MARCH 15, 2012 AND IS THE ONE THAT |
| | APPLIES TO THIS PROJECT. PLEASE CORRECT. |
| | |
| | 2) SPECIFY THE DESIGN CRITERIA ON THE PLANS. THE WIND |
| | SPEED FOR THIS PROJECT IS 170 MPH VULT AND THE EXPOSURE |
| | CATEGORY IS B. FBC R301.2.1.1 AND R301.2.1.4 |
| | |
| | 3) PLEASE UPDATE THE REFERENCED DESIGN STANDARDS ON |
| | SHEET A4 TO COMPLY WITH THE 2010 FBC. THE 2008 EDITIONS |
| | OF ACI 315, 301 AND 530 / TMS 402, 602 / ASCE 5 , 6 ARE |
| | LISTED IN THE REFERENCED STANDARDS IN CHAPTER 43 OF THE |
| | 2010 FBC. |
| | |
| | 4) SPECIFY THE COMPONENT AND CLADDING WIND LOAD |
| | PRESSURES FOR THE WINDOWS AND DOORS ON THE PLANS. FBC |
| | R301.2.1 THE WIND LOAD SCHEDULE ON A4 ONLY LISTS WALL |
| | PRESSURES FOR 50 SQFT. IF YOU WISH TO PROVIDE WORST |
| | CASE WIND LOAD PRESSURES USE THE 10 SQFT AREA |
| | PRESSURES. |
| | |
| | 5) DOOR #8 FROM THE GARAGE INTO THE RESIDENCE IS |
| | SPECIFIED IN THE SCHEDULE AS HOLLOW CORE. FBC R301.5.1 |
| | REQUIRES SPECIFIC TYPES OF DOORS AT THIS LOCATION. |
| | PLEASE REVISE. |
| | |
| | 6) THE ROOF ZONE DIAGRAM ON SHEET A4 IS INCORRECT. THE |
| | OUTSIDE CORNERS OF THE HIP ROOF ARE DESIGNATED AS ZONE |
| | 3. SEE FIGURE R301.2(7). |
| | |
| | 7) THE ROOM DIMENSIONS ARE MISSING FROM THE FLOOR |
| | PLANS. PLEASE CORRECT. CITY AMENDMENTS 107.3.5 AND R304 |
| | |
| | 8) THE TRUSS CONNECTOR SCHEDULE ON A4 DOES NOT SPECIFY |
| | THE MODEL NUMBER, LOADS, OR PRODUCT APPROVAL NUMBER FOR |
| | TRUSS ANCHORS A & B. FBC R802.1.6.5 AND DCA RULE 9N-3 |
| | |
| | 9) THE ENERGY CALCULATION FORMS ARE NOT SIGNED BY THE |
| | PREPARER OR THE OWNER/AGENT. FBC ENERGY CONSERVATION |
| | 405.4.2 |
| | |
| | 10) THE ENERGY CALCULATION FORM SPECIFIES A 14 SEER |
| | COOLING SYSTEM AND THE MANUAL J CALCULATIONS SPECIFY A |
| | 13 SEER SYSTEM. PLEASE CORRECT. FBC ENERGY CONSERVATION |
| | 405.3 |
| | |
| | 11) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER |
| | CITY AMENDMENTS 107.3.4.1. |
| | |
| | 12) SUBMIT TWO COPIES OF THE 2010 COVERSHEET, THE |
| | PRODUCT CERTIFICATION AND INSTALLATION INSTRUCTIONS FOR |
| | EXTERIOR DOOR FL#8228. DCA RULE 9N-3 |
| | |
| | 13) SUBMIT TWO COPIES OF THE EVALUATION REPORT AND |
| | INSTALLATION INSTRUCTIONS FOR THE OVER HEAD GARAGE DOOR |
| | FL # 5302. DCA RULE 9N-3 |
| | |
| | 14) SUBMIT TWO COPIES OF THE 2010 COVERSHEET FOR THE |
| | TAMKO SHINGLES FL# 1956. DCA RULE 9N-3 |
| | |
| | 15) SUBMIT TWO COPIES OF THE 2010 COVERSHEET, THE |
| | PRODUCT EVALUATION REPORT AND INSTALLATION INSTRUCTIONS |
| | FOR THE STORM PANELS FL #11968. ALSO SUBMIT TWO COPIES |
| | OF A KEY PLAN AND AN INSTALLATION SCHEDULE. DCA RULE |
| | 9N-3 AND CITY AMENDMENTS 107.2.1.3 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |