Plan Review Notes
Plan Review Notes For Permit 12050836
Permit Number 12050836
Review Stop B
Sequence Number 1
Notes
Date Text
2012-06-14 13:46:492010 FBC
  
 DENIED BY BUILDING
  
 1) THE GENERAL NOTES ON SHEET A1 AND THE STRUCTURAL
 NOTES ON A4 SPECIFY THE 2007 FBC. THE 2010 FBC WENT
 INTO EFFECT ON MARCH 15, 2012 AND IS THE ONE THAT
 APPLIES TO THIS PROJECT. PLEASE CORRECT.
  
 2) SPECIFY THE DESIGN CRITERIA ON THE PLANS. THE WIND
 SPEED FOR THIS PROJECT IS 170 MPH VULT AND THE EXPOSURE
 CATEGORY IS B. FBC R301.2.1.1 AND R301.2.1.4
  
 3) PLEASE UPDATE THE REFERENCED DESIGN STANDARDS ON
 SHEET A4 TO COMPLY WITH THE 2010 FBC. THE 2008 EDITIONS
 OF ACI 315, 301 AND 530 / TMS 402, 602 / ASCE 5 , 6 ARE
 LISTED IN THE REFERENCED STANDARDS IN CHAPTER 43 OF THE
 2010 FBC.
  
 4) SPECIFY THE COMPONENT AND CLADDING WIND LOAD
 PRESSURES FOR THE WINDOWS AND DOORS ON THE PLANS. FBC
 R301.2.1 THE WIND LOAD SCHEDULE ON A4 ONLY LISTS WALL
 PRESSURES FOR 50 SQFT. IF YOU WISH TO PROVIDE WORST
 CASE WIND LOAD PRESSURES USE THE 10 SQFT AREA
 PRESSURES.
  
 5) DOOR #8 FROM THE GARAGE INTO THE RESIDENCE IS
 SPECIFIED IN THE SCHEDULE AS HOLLOW CORE. FBC R301.5.1
 REQUIRES SPECIFIC TYPES OF DOORS AT THIS LOCATION.
 PLEASE REVISE.
  
 6) THE ROOF ZONE DIAGRAM ON SHEET A4 IS INCORRECT. THE
 OUTSIDE CORNERS OF THE HIP ROOF ARE DESIGNATED AS ZONE
 3. SEE FIGURE R301.2(7).
  
 7) THE ROOM DIMENSIONS ARE MISSING FROM THE FLOOR
 PLANS. PLEASE CORRECT. CITY AMENDMENTS 107.3.5 AND R304
  
 8) THE TRUSS CONNECTOR SCHEDULE ON A4 DOES NOT SPECIFY
 THE MODEL NUMBER, LOADS, OR PRODUCT APPROVAL NUMBER FOR
 TRUSS ANCHORS A & B. FBC R802.1.6.5 AND DCA RULE 9N-3
  
 9) THE ENERGY CALCULATION FORMS ARE NOT SIGNED BY THE
 PREPARER OR THE OWNER/AGENT. FBC ENERGY CONSERVATION
 405.4.2
  
 10) THE ENERGY CALCULATION FORM SPECIFIES A 14 SEER
 COOLING SYSTEM AND THE MANUAL J CALCULATIONS SPECIFY A
 13 SEER SYSTEM. PLEASE CORRECT. FBC ENERGY CONSERVATION
 405.3
  
 11) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER
 CITY AMENDMENTS 107.3.4.1.
  
 12) SUBMIT TWO COPIES OF THE 2010 COVERSHEET, THE
 PRODUCT CERTIFICATION AND INSTALLATION INSTRUCTIONS FOR
 EXTERIOR DOOR FL#8228. DCA RULE 9N-3
  
 13) SUBMIT TWO COPIES OF THE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS FOR THE OVER HEAD GARAGE DOOR
 FL # 5302. DCA RULE 9N-3
  
 14) SUBMIT TWO COPIES OF THE 2010 COVERSHEET FOR THE
 TAMKO SHINGLES FL# 1956. DCA RULE 9N-3
  
 15) SUBMIT TWO COPIES OF THE 2010 COVERSHEET, THE
 PRODUCT EVALUATION REPORT AND INSTALLATION INSTRUCTIONS
 FOR THE STORM PANELS FL #11968. ALSO SUBMIT TWO COPIES
 OF A KEY PLAN AND AN INSTALLATION SCHEDULE. DCA RULE
 9N-3 AND CITY AMENDMENTS 107.2.1.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]