| Plan Review Notes For Permit 12050798 |
| Permit Number |
12050798 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-30 10:23:03 | 1661 WORTHINGTON ROAD - SUITE #100 & #150 | | | PERMIT #12050798 | | | MASTER #12040636 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ONE CEILING NOTIFICATION DEVICE IS INSUFFICIENT FOR THE | | | LARGE OPEN OFFICE AREA. SHOW ADJACENT DEVICE LOCATIONS | | | SO COVERAGE CAN BE VERIFIED. | | | | | | FIRE ALARM SHOP DRAWING SCOPE IS INCONSISTENT WITH THE | | | SCOPE OF WORK SHOWN ON SHEET E-2 OF THE SEALED | | | CONSTRUCTION DOCUMENTS OF MASTER PERMIT #12040636. | | | ADDITIONAL STROBE NOTIFICATION APPLIANCES APPEAR TO | | | HAVE BEEN ADDED IN RESTROOMS. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|