| Plan Review Notes For Permit 12050775 |
| Permit Number |
12050775 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-30 09:45:01 | 1225 PALM BEACH LAKES BOULEVARD | | | PERMIT #12050775 | | | MASTER #11050304 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION | | | (#302). | | | | | | FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND | | | IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|