| 2012-06-08 10:42:57 | BUILDING PLAN REVIEW |
| | PERMIT: 12050770 |
| | ADD: 401 S DIXIE 1ST FLOOR |
| | CONT:TBD |
| | TEL: (561)389-3887 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A3.0 MISSING THE WIND DESIGN CRITERIA: |
| | 1609.6.2 WIND DESIGN PROCEDURES |
| | 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 1.5) COMPONENTS & CLADDING FOR PRESSURES +/-. |
| | |
| | 2) SHEET A3.0 ELEVATIONS INDICATE THE OPENINGS TO BE |
| | OVER 120" TALL, 10'-6". THE VERTICAL OPENING EXCEEDS |
| | THE TABLES IN THE SUBMITTED PRODUCT APPROVALS EITHER |
| | NEW APPROVALS WOULD BE REQUIRED OR MULLIONS THAT WILL |
| | MEET THE VERTICAL LENGTH REQUIREMENTS AND ASSOCATED |
| | PRESSUES. |
| | 107.3.1*, FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS / MULLIONS |
| | |
| | |
| | JAMES A. WITMER CBO |