| Plan Review Notes For Permit 12050721 |
| Permit Number |
12050721 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-06 12:45:13 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. IMPACT PROTECTION REQUIRED, FBC R 301.2.1.2. PROVIDE | | | PRODUCT APPROVALS AND, IF SHUTTERS ARE USED, COMPLETE | | | THE SAMPLE INSTALLATION SCHEDULE (AVAILABLE IN THE | | | LOBBY AND AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/ | | | SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | APPLICATION STATES THAT SHUTTERS ARE EXISTING. SHUTTERS | | | MUST BE FBC COMPLIANT, PERMITTED AND INSPECTED TO | | | QUALIFY AS "IMPACT PROTECTION." | | | | | | 2. PROVIDE SIZES OF PROPOSED WINDOWS, FBC R310, FBC EB | | | 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN | | | 5% FOR BEDROOMS. PROVIDE WINDOW TYPE OF THE WINDOWS | | | WHICH WERE REMOVED (FOR EXAMPLE, AWNING, JALOUSY, | | | SINGLE HUNG, ETC.). PLEASE REVISE PLAN TO INCLUDE THIS | | | INFORMATION (SIZES, EXISTING WINDOW TYPE). |
|