| Plan Review Notes For Permit 12050713 |
| Permit Number |
12050713 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-23 15:31:40 | RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 10-1230.03 SUBMITTED. NEED NAIL ENHANCING TO MEET THE | | | DESIGN PRESSURES AS REQUIRED BY SEC. 1609. PROVIDE 2 | | | COPIES WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTES. | | | | | | 2- PROVIDE TAS 105 FASTENER WITHDRAWAL TEST AS REQUIRED | | | BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA SUBMITTED. | | | NEED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF | | | SEC. 1609. PROVIDE 2 COPIES WITH ORIGINAL SEAL AND | | | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. | | | | | | 3- FOR YOUR INFORMATION: ANY ROOF EQUIPMENT REMOVAL | | | REQUIRES SEPARATE PERMITS. AND, ANY RETROFIT ROOF | | | DRAINS REQUIRE PLUMBING REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|