2012-05-23 15:31:40RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 10-1230.03 SUBMITTED. NEED NAIL ENHANCING TO MEET THE
 DESIGN PRESSURES AS REQUIRED BY SEC. 1609. PROVIDE 2
 COPIES WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
  
 2- PROVIDE TAS 105 FASTENER WITHDRAWAL TEST AS REQUIRED
 BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA SUBMITTED.
 NEED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. 1609. PROVIDE 2 COPIES WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 3- FOR YOUR INFORMATION: ANY ROOF EQUIPMENT REMOVAL
 REQUIRES SEPARATE PERMITS. AND, ANY RETROFIT ROOF
 DRAINS REQUIRE PLUMBING REVIEW.
  