| 2012-07-18 16:34:11 | BUILDING PLAN REVIEW |
| | PERMIT: 12050711 |
| | ADD: 1801 S FLAGLER DR # 204 |
| | CONT: D L PORTER CONSTRUCTORS, INC (TBD) |
| | TEL: (941)650-3311 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1)COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | 3A)2ND REQUEST, PLANS INDICATE NEW WOOD FLOORS, PLEASE |
| | PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE |
| | BORNE SOUND TRANSMITION. THE FLOORING/ CEILING ASSEMBLY |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492 SUBMIT REPORT. |
| | |
| | 3B) ASH 3/8 INCH HARDWOOD FLOORING PLEASE PROVIDE |
| | COMPLIANCE WITH SECTION 2010 FBC-B 603.1.2(2) |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | OR |
| | 805.1.3 INSULATING BOARDS. COMBUSTIBLE INSULATING |
| | BOARDS NOT MORE THAN 1/2 INCH (12.7 MM) THICK AND |
| | COVERED WITH APPROVED FINISH FLOORING ARE PERMITTED |
| | WHERE ATTACHED DIRECTLY TO A NONCOMBUSTIBLE FLOOR |
| | ASSEMBLY OR TO WOOD SUBFLOORING ATTACHED TO SLEEPERS AS |
| | PROVIDED FOR IN SECTION 805.1.1. |
| | OR |
| | 804.3 TESTING AND IDENTIFICATION. INTERIOR FLOOR FINISH |
| | AND FLOOR COVERING MATERIALS SHALL BE TESTED BY AN |
| | APPROVED AGENCY IN ACCORDANCE WITH NFPA 253 AND |
| | IDENTIFIED BY A HANG TAG OR OTHER SUITABLE METHOD SO AS |
| | TO IDENTIFY THE MANUFACTURER OR SUPPLIER AND STYLE, AND |
| | SHALL INDICATE THE INTERIOR FLOOR FINISH OR FLOOR |
| | COVERING CLASSIFICATION ACCORDING TO SECTION 804.2. |
| | CARPET-TYPE FLOOR COVERINGS SHALL BE TESTED AS PROPOSED |
| | FOR USE, INCLUDING UNDERLAYMENT. TEST REPORTS |
| | CONFIRMING THE INFORMATION PROVIDED IN THE |
| | MANUFACTURER'S PRODUCT IDENTIFICATION SHALL BE |
| | FURNISHED TO THE BUILDING OFFICIAL UPON REQUEST. |
| | |
| | 4-6) NOT PART OF SCOPE OF WORK. |
| | |
| | 7) 2ND REQUEST, SHEET A1.01 NOTE # 8 INDICATES THE |
| | INSTALATION OF A NEW SOFFIT/ DROPPED CEILING BUT THERE |
| | IS NO FRAMING INFORMATION, TYPE OF FINISH ON THE |
| | SOFFIT, LIMITS OF DEFLECTION, |
| | 2010 FBC-B 2506.2, TABLE 2506.2 STEEL STUDS NON-LOAD |
| | BEARING ASTM C 645. |
| | |
| | JAMES A. WITMER CBO |