| Plan Review Notes For Permit 12050659 |
| Permit Number |
12050659 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-31 12:06:42 | PASSED WITH A PROVISO. | | | | | | PROVISO: | | | | | | AFCI PROTECTED CIRCUITS ARE REQUIRED. NEC 210.12 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314 | | | |
|