| 2012-06-11 15:38:37 | BUILDING PLAN REVIEW |
| | PERMIT: 12050636 |
| | ADD: 901 45TH ST |
| | CONT: WESTBROOKE |
| | TEL: (561) 239-7133 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING PER |
| | FS 553.79(7). |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 1B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 1C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | ------------------------------------------------------- |
| | ----------------------------------- |
| | |
| | 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | ------------------------------------------------------- |
| | ------------------------------------- |
| | |
| | 1E) A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE |
| | ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR FOR LARGE PROJECTS OS SIMILAR DESIGN. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO |
| | CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED FOR WORK |
| | WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2) FOR PERMIT ISSUANCE OF A THRESHOLD BUILDING (3) SETS |
| | OF PLANS AND ALL ASSOCIATED DOCUMENTS WILL BE REQUIRED, |
| | (1) SET FOR THE THRESHOLD INSPECTORS OWN RECORDS. |
| | |
| | 3) SHEET S-101 FOUNDATION DESIGN INDICATES A SOILS |
| | REPORT COMPLETED BY GFA INTERNATIONAL REPORT NUMBER |
| | 10-0185 APRIL 16, 2010. 2010 FBC-B 1803.6 |
| | |
| | REPORTS. THE SOIL CLASSIFICATION AND DESIGN |
| | LOAD-BEARING CAPACITY SHALL BE SHOWN ON THE |
| | CONSTRUCTION DOCUMENTS. WHERE REQUIRED BY THE BUILDING |
| | OFFICIAL, A WRITTEN REPORT OF THE INVESTIGATION SHALL |
| | BE SUBMITTED THAT INCLUDES, BUT NEED NOT BE LIMITED TO, |
| | THE FOLLOWING INFORMATION: |
| | |
| | 1. A PLOT SHOWING THE LOCATION OF TEST BORINGS AND/OR |
| | EXCAVATIONS. |
| | |
| | 2. A COMPLETE RECORD OF THE SOIL SAMPLES. |
| | |
| | 3. A RECORD OF THE SOIL PROFILE. |
| | |
| | 4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. |
| | |
| | 5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN |
| | CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING |
| | CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO |
| | MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF |
| | THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT |
| | AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT |
| | LOADS. |
| | |
| | 6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. |
| | |
| | 7. PILE AND PIER FOUNDATION INFORMATION IN ACCORDANCE |
| | WITH SECTION 1808.2.2. |
| | |
| | 8. SPECIAL DESIGN AND CONSTRUCTION PROVISIONS FOR |
| | FOOTINGS OR FOUNDATIONS FOUNDED ON EXPANSIVE SOILS, AS |
| | NECESSARY. |
| | |
| | 9. COMPACTED FILL MATERIAL PROPERTIES AND TESTING IN |
| | ACCORDANCE WITH SECTION 1803.5. |
| | |
| | 4A) SHEET S-001 EXSPANSION ANCHORS REQUIRES REPORT # |
| | ERS-1917, 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4B) SHEET S-001 ADHESIVE DOWELED-ANCHORS REQUIRES |
| | REPORT ER-5193. ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4C) SHEET S-001 INTHE ABOVE MENTIONED HEADINGS FOR |
| | COMMENTS 4A & 4B THE TERM "OR EQUAL" APPEARS PLEASE |
| | REVIEW 2010 FBC-B WPB ADMINISTRATIVE AMENDMENT 107.2.1 |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 5) GE HEALTHCARE TECHNOLOGIES SHEETS A1, S1 & S2 ARE |
| | NEITHER SIGNED NOR SEALED WHO IS TAKING RESPONSIBILITY |
| | FOR THESE DESIGNS? |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | IF TO BE CONSIDERED SHOP DRAWINGS THEN : |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 6) S-302 DETAIL D-1 INDICATES A ISOLATED FOUNDATION |
| | DESIGN WITH THE SLOPE OF REPOSE AT A 45 DEGREE ANGLE |
| | PLEASE REVIEW 2010 FBC-B 1809.6 LOCATION OF FOOTINGS. |
| | ISOLATED FOOTINGS. FOOTINGS ON GRANULAR SOIL SHALL BE |
| | SO LOCATED THAT THE LINE DRAWN BETWEEN THE LOWER EDGES |
| | OF ADJOINING FOOTINGS SHALL NOT HAVE A SLOPE STEEPER |
| | THAN 30 DEGREES (0.52 RAD) WITH THE HORIZONTAL, UNLESS |
| | THE MATERIAL SUPPORTING THE HIGHER FOOTING IS BRACED OR |
| | RETAINED OR OTHERWISE LATERALLY SUPPORTED IN AN |
| | APPROVED MANNER OR A GREATER SLOPE HAS BEEN PROPERLY |
| | ESTABLISHED BY ENGINEERING ANALYSIS. IS THIS |
| | INFORMATION IN THE GFA SOILS REPORT? |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | RULE 9N-03(31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, INCLUDING ROOF |
| | INSULATION |
| | (E) SHUTTERS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 10) EFIS WALL SYSTEMS ARE TO COMPLY WITH 2010 FBC-B |
| | 2603.5.4 FLAME SPREAD AND SMOKE DEVELOPMENT INDEXES. |
| | |
| | 11) SHEET A-500 DETAILS C2 & D2 BOTH INDICATES USE OF |
| | 3/4 INCH EXTERIOR GRADE PLYWOOD, PLEASE REVIEW 2010 |
| | FBC-B 603.1.1 AND ALLOWABLE USES OF FIRE RETARDENT |
| | TREATED WOOD. |
| | |
| | 12) SHEET A-500 DETAIL A4 DOES NOT PROVIDE INFORMATION |
| | IN REGARDS TO DAMPPROOFING/ WATERPROOFING, THE PLANS |
| | ALSO INDICATE THE USE OF EFIS BELOW GRADE PLEASE |
| | PROVIDE |
| | MANUFACTURERS SPECIFICATIONS FOR THIS USAGE IN AREAS |
| | WHERE THERE IS A HIGH CONCENTRATION OF TERMITES. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 13) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B |
| | 435.1.1-435.1.2 SHEILDING X-RAYS. 435.1.3 WILL NEED |
| | DEPARTMENT OF HEALTH REVIEW. |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |