Notes
Date Text
2012-06-01 16:25:062010 FBC
  
 DENIED BY BUILDING
  
 1) THE SPACING OF THE VERTICAL REINFORCEMENT IN THE
 MASONRY WALLS APPEARS TO BE EXCESSIVE. PLEASE REVIEW
 SHEET A-1. FBC R609.3.3
  
 2) SPECIFIED THE REQUIRED COMPONENT AND CLADDING
 PRESSURES FOR THE WINDOWS AND DOORS ON THE PLANS. FBC
 R301.2.1 AND CITY AMENDMENTS 107.3.5.3
  
 3) THE CONSTRUCTION TYPE IS SPECIFIED AS TYPE V ON THE
 COVER SHEET. THE CONSTRUCTION TYPE IS TYPE V-B PER FBC
 TABLE 601.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER
 CITY AMENDMENTS 107.3.4.1.
  
 5) TWO COPIES OF THE PRODUCTS APPROVALS ARE REQUIRED
 PER CITY AMENDMENTS 107.1. ONLY ONE COPY OF THE PRODUCT
 APPROVAL FOR THE ROOF SHINGLES WAS SUBMITTED.
  
 6) THE VALUE OF THE PROJECT SPECIFIED FOR THE ADDITION
 IS TOO LOW. PER CITY AMENDMENT 109.3, FOR PERMITTING
 PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD AND PROFIT;
 EXCLUDING ONLY THE LAND VALUE. BASED ON ICC VALUATION
 DATA, THE VALUATION IS $95,438.76 FOR THE ADDITION.
  
 7) IN ORDER TO SPEED THE REVIEW PROCESS, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 HAVE BEEN ADDRESSED.
  