Plan Review Notes
Plan Review Notes For Permit 12050625
Permit Number 12050625
Review Stop B
Sequence Number 1
Notes
Date Text
2012-06-04 14:47:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 107.2.1, SUBMIT A PLAN WHICH CLEARLY SHOWS SCOPE
 OF WORK AND LOCATION OF PROPOSED WORK.
  
 2.. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 3. PROVIDE A DETAIL FOR THE WOOD REPLACEMENT. SCOPE OF
 REPAIR NOT CLEAR.
  
 4. PROVIDE A DEMO PLAN FOR THE KITCHEN AND A PROPOSED
 NEW PLAN. IF THE SAME LAYOUT IS TO BE MAINTAINED, SAME
 SIZE CABINEST IN SAME CONFIGURATION, PLEASE INDICATE ON
 THE PLAN (AND A PROPOSED FLOOR PLAN WILL NOT BE
 REQUIRED).
  
  